Control_Flippingbook_July 2024
CONTACTORS AND OVERLOAD RELAYS, CONTROL SECTION 2
2-38
— 4-pole contactors
IEC
AC-1 Rated operational current θ ≤ 40 °C, 690 V A
25 25
30 30
45 45
55 55
70 60
100
125 105
UL/CSA General use rating
600 V
A
80
AF09 AF16 AF26 AF38 AF40 AF52
AF80
Type
AC / DC Control supply
AF09 AF16 AF26 AF38 AF40 AF52
AF80
AC Control supply
Type
AF09 AF16 AF26 AF38 AF40 AF52
AF80
DC Control supply
Type
θ ≤ 40 °C θ ≤ 60 °C 1 θ ≤ 70 °C
A A A
25 25 22
30 30 26
45 40 32 10
55 45 37 16
70 60 50 35
100
125 105
AC-1 Rated operational current 690 V
80 70 35
IEC
90 50
With conductor cross sectional area Rated operational voltage Ue max.
mm²
4
6
V
690
690
690
690
690
690
690
1 θ ≤ 55 °C for EK550, EK1000 contactors
Main accessories
CA4-10 (1 x N.O.), CA4-01 (1 x N.C.) CAL4-11 (1 x N.O. + 1 x N.C.) TEF4-ON TEF4-OFF VM4
Front mounting Side mounting
Auxiliary contact blocks
Timers
Electronic
VM96-4
Mechanical Mechanical / Electrical Varistor + RC (AC / DC)
Interlocking units
VEM4 Built-in surge protection
Surge suppressors