NEMA FULL VOLTAGE POWER DEVICES, CONTROL SECTION 1
— CR413 magnetic starters 2 Speed – 1 winding, nonfusible and fusible disconnect type
Part number configuration Valid for NEMA sizes 0-4
— Step 8 (digit 16) select pilot device
Pilot light (heavy duty CR104P style) type
Color — functionality
Code
None
A 2 3 5 S T Y
Red and amber across coils Red and green across coils
LED lights
Red and amber across coils and unwired green
Red and amber across coils Red and green across coils
Push-to-test lights
Red and amber across coils and unwired green
— Step 9 (digit 17) select control options
Device
Code
None
A
1 relay, 2NO-2NC, 24/120 V coil - unwired
B 5 C 5
2 relays, 24/120 V coil - unwired
DIN rail - for customer use
D E
12 point terminal strip - unwired (12 PT strip)
Space heater w/ NC contact
H 6
1 relay + 12 PT strip 2 relays + 12 PT strip
J 5
K 5 L 6
DIN rail + 12 PT strip + space heater 2 relays + 12 PT strip + space heater
M 5,6
Time delay on relay, 24/120 V coil - unwired (TD) Time delay off relay, 24/120 V coil - unwired (TD)
N 5 P 5 R 5 S 5
12 PT strip + TD ON 12 PT strip + TD OFF
12 PT strip + space heater + TD ON 12 PT strip + space heater + TD OFF
T 5,6 U 5,6
5 Relay/timer coil voltage is equivalent to CPT secondary voltage. Requires minimum 100 extra VA CPT option. 6 Maximum number of auxiliary contacts shall be reduced by 1.
General note: On NEMA size 3 and 4 starters, if selecting factory installed and wired operator devices (push buttons, selector switches, and/or pilot lights) then control circuit fusing, a control power transformer, or 120 V separate sourced control is required when the protective device is rated greater than 100 amps.