City of Morgan Hill Sewer System Master Plan 2017
Table ES.1 Sewer System Performance and Design Criteria Sewer System Master Plan City of Morgan Hill
PRELIMINARY
Pipeline Criteria Peak Dry Weather Flow Criteria
Diameter (in) 8 to 12 > 12
Maximum Allowable d/D
Existing Trunks
Proposed Trunks
0.90 0.90
0.75 0.75
Peak Wet Weather Flow Criteria
Hydraulic Grade Line (HGL) should be at least 3 feet below the manhole rim Pipe Minimum Size Grade (in) (ft/ft) (mgd) (cfs) 8 0.0026 0.36 0.55 10 0.0019 0.56 0.87 12 0.0015 0.79 1.23 15 0.0011 1.28 1.98 18 0.0009 1.78 2.75 21 0.0007 2.43 3.76 24 0.0006 3.27 5.05 27 0.0005 4.18 6.47 30 0.0004 5.13 7.94 33 0.0004 6.04 9.34 36 0.0004 7.61 11.78 42 0.0003 10.27 15.90 1/7/2016 Capacity (n = 0.013)
Made with FlippingBook - Online magazine maker