Control_Flippingbook_NOV 2024

NEMA FULL VOLTAGE POWER DEVICES, CONTROL SECTION 1

1-117

— Solid-state overload relays CR324X solid-state overload relays

— Solid-state overload relays

Panel mount Ordering code

MRO and replacement

Setting range amps

NEMA size Fuse max. amps

Breaker max amps

Continuous amp rating

Ordering code CR324CXCS CR324CXDS CR324CXES CR324CXFS CR324CXGS CR324CXHS CR324DXGS CR324DXHS CR324DXJS CR324FXKS 1 CR324FXLS 1 CR324FXMS 1 CR324FXKS 1 CR324FXLS 1 CR324FXMS 1 CR324GXNS 2 CR324GXPS 2 CR324GXQS 2 CR324HXSK 3 CR324HXTK 3 CR324HXSS 4

0.4–0.85 0.8–1.7 1.6–3.4 3.2–6.8 6.5–13.5 6.5–13.5 13–27 25–50 17–35 35–70 65–135 13–27

00–1 00–1 00–1 00–1 00–1 00–1

3 6

15 15 15 25 50

27 27 27 27 27 27 45 45 45 90 90 90

CR324CXCP CR324CXDP CR324CXEP CR324CXFP CR324CXGP CR324CXHP CR324DXGP CR324DXHP CR324DXJP CR324FXKP CR324FXLP CR324FXMP CR324FXKP CR324FXLP CR324FXMP

12 25 50

100

100

2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 6

50

50

100 200 125 250 500 125 250 500

100 200 125 250 400 125 250 400 400 800 800 800 800 800 –

17–35 35–70

135 135 135

65–135

35–70

– – – – – – –

65–135 130–270 130–270 260–540 130–270 260–540

500 600

1200 1200 1200 1200

CR324HXTS 4 1 Reset is approximately 1" longer than on equivalent bimetal overloads. For ABB 300-line enclosures, perform the actions noted in the enclosure reset extension type table 2 May be used as replacement for bimetal overload on size 5 starters. Use existing CTs. 3 Must be used as solid-state replacement for bimetal overloads on size 6; since CT ratio changes, CTs are included. 4 May be used as a replacement for existing solid-state overload on size 6. Use existing CTs.

Enclosure reset extension type

Adjustment required

Threaded rod (standard)

Cut threaded shaft 1" and adjust for 1 ⁄

8 " gap

“U” style, 2 1 ⁄ “U” style, 1 1 ⁄

8 " long 2 " long

Replace extension with ordering code 55-512811G005 Replace extension with ordering code 55-512811G002

— Solid-state overload relay options Item

NEMA size

Voltage 120 V AC

Ordering code CR324XRRM02 CR324CXPMA CR324DXPMA

Remote reset

1–6

Panel-mount adapter

1 2

– –

Please reference the NEMA full voltage power devices catalog for additional technical data and dimensional drawings.