NEMA FULL VOLTAGE POWER DEVICES, CONTROL SECTION 1

1-74

— Enclosed combination magnetic starters CR412 2-speed/1-winding, thermal magnetic circuit breaker

Ordering code configuration Valid for NEMA sizes 0–4

Digits:

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

C R

Steps:

Step 1

Step 2

Step 3

Step 4 Step 5 Step 6 Step 7 Step 8 Step 9

To configure the ordering code, use the tables below to fill in the digit boxes with the appropriate code.

— Step 7 (digit 15) select pushbutton/selector switch Pushbutton/selector switch — heavy duty

Code

None

A

Fast/slow/stop pushbutton High/low/off pushbutton

J

K L

High/low pushbutton and hand-off-auto (HOA) selector switch Fast/slow pushbutton and hand-off-auto (HOA) selector switch Hand-off-auto (HOA) and slow/fast selector switches

M

P R T U V

Hand-off-auto (HOA) and low/high selector switches

Slow-off-fast selector switch Low-off-high selector switch Fast-slow-off-auto selector switch High-low-off-auto selector switch

W

— Step 8 (digit 16) select pilot device Pilot light (heavy duty CR104P style) type

Color — functionality

Code

None

A 2 3 5 S T Y

LED lights

Red and amber across coils Red and green across coils

Red and amber across coils and unwired green

Push-to-test lights

Red and amber across coils Red and green across coils

Red and amber across coils and unwired green

— Step 9 (digit 17) select control options Device

Code

None

A

1 relay, 2 NO-2 NC, 24/120 V coil — unwired

B 5 C 5

2 relays, 24/120 V coil — unwired

DIN rail — for customer use

D E

12 point terminal strip — unwired (12 PT strip)

Space heater with NC contact

H 6

1 relay + 12 PT strip 2 relays + 12 PT strip

J 5

K 5 L 6

DIN rail + 12 PT strip + space heater 2 relays + 12 PT strip + space heater

M 5,6

Time delay on relay, 24/120 V coil — unwired (TD) Time delay off relay, 24/120 V coil — unwired (TD)

N 5 P 5 R 5 S 5

12 PT strip + TD ON 12 PT strip + TD OFF

12 PT strip + space heater + TD ON 12 PT strip + space heater + TD OFF

T 5,6 U 5,6

5 Relay/timer coil voltage is equivalent to CPT secondary voltage. Requires minimum 100 extra VA CPT option. 6 Maximum number of auxiliary contacts shall be reduced by 1.

General note: On NEMA size 3 and 4 starters, if selecting factory installed and wired operator devices (pushbuttons, selector switches and/or pilot lights), then control circuit fusing, a control power transformer or 120 V separate sourced control is required when the protective device is rated greater than 100 amps.

Made with FlippingBook - Online Brochure Maker