Control Catalog Flippingbook

SOFTSTARTERS, CONTROL SECTION 9

9-8

— PSR Technical data

Softstarter types

PSR3 PSR6 PSR9 PSR12 PSR16 PSR25 PSR30 PSR37 PSR45 PSR60 PSR72 PSR85 PSR105 0.7 W 2.9 W 6.5 W 11.5 W 20.5 W 25 W 36 W 5.5 W 8.1 W 3.6 W 5.2 W 7.2 W 6.6 W

Max. Power loss at rated I e

Number of starts per hour using PSR softstarters Motor current Starts/hour without auxiliary fan I e

Technical data Rated insulation voltage U i Rated operational voltage U e Rated control supply voltage U s

600 V

208...600 V +10%/-15%, 50/60 Hz ±5%

10 20 30 40 50 60 80 100 PSR3 PSR3 PSR3 PSR3 PSR3 PSR3 PSR3 PSR6 PSR6 PSR6 PSR6 PSR6 PSR6 PSR9 PSR9 PSR9 PSR9 PSR9 PSR9 PSR12 PSR12 PSR12 PSR16 PSR25 PSR12 PSR12 PSR12 PSR16 PSR25 PSR25 PSR30 PSR30 PSR16 PSR25 PSR25 PSR25 PSR30 PSR30 PSR37 PSR37 PSR25 PSR30 PSR37 PSR37 PSR37 PSR45 PSR45 PSR60 PSR30 PSR37 PSR37 PSR45 PSR45 PSR60 PSR60 PSR72 PSR37 PSR45 PSR45 PSR60 PSR60 PSR72 PSR85 PSR105 PSR45 PSR45 PSR60 PSR60 PSR72 PSR85 PSR105 -

100...240 V AC, 50/60Hz ±5% or 24 V AC/DC, +10%/-15%

3 A 6 A 9 A

Starting capacity at I e Maximum altitude

4 x I e for 6 sec.

4000 m (13123 ft)³

12 A 16 A 25 A 30 A 37 A 45 A 60 A 72 A 85 A

Number of starts per hour Standard

10 ¹ 20 ¹

With aux. fan

Ambient temperature During operation

-25...+60 ° C (-13...+140 °F)² -40...+70 ° C (-40...+158 °F)

During storage

PSR60 PSR60 PSR72 PSR85 PSR105 PSR105

- - - -

- - - -

Degree of protection Main circuit

PSR72 PSR85 PSR105 PSR105

- - -

- - -

PSR3 - PSR30: IP20 PSR37 - PSR105: IP10 PSR3 - PSR30: IP20

PSR85 PSR105 PSR105

- -

105 A

PSR105

-

-

Control circuit

Power consumption At 100...240 V AC

PSR3 - PSR30: 12 VA PSR37 - PSR105 10 VA PSR3 - PSR30: 5 W PSR37 - PSR105: 10 VA

Number of starts per hour using PSR softstarters Motor current Starts/hour with auxiliary fan I e

At 24 V AC/DC

10 20 30 40 50 60 80 100 PSR3 PSR3 PSR3 PSR3 PSR3 PSR3 PSR3 PSR3 PSR6 PSR6 PSR6 PSR6 PSR6 PSR6 PSR6 PSR9 PSR9 PSR9 PSR9 PSR9 PSR9 PSR12 PSR12 PSR12 PSR12 PSR12 PSR12 PSR12 PSR12 PSR16 PSR25 PSR25 PSR16 PSR16 PSR25 PSR25 PSR25 PSR25 PSR30 PSR30 PSR25 PSR2 PSR30 PSR37 PSR37 PSR37 PSR37 PSR45 PSR30 PSR30 PSR37 PSR37 PSR45 PSR45 PSR45 PSR45 PSR37 PSR37 PSR45 PSR45 PSR45 PSR45 PSR60 PSR60 PSR45 PSR45 PSR45 PSR60 PSR60 PSR60 PSR72 PSR72 PSR60 PSR60 PSR60 PSR72 PSR72 PSR85 PSR105 -

3 A 6 A 9 A

Signal relays for run signal: PSR3.. 105 Resistive load

3 A

AC-15 (contactor)

0.5 A

12 A 16 A 25 A 30 A 37 A 45 A 60 A 72 A 85 A

Signal relays for top of ramp signal: PSR25... 105 Resistive load

3 A

AC-15 (contactor)

0.5 A

LED For On/Ready

Green Green

For Run/Top of ramp Settings Ramp time during start Ramp time during stop Initial- and end voltage

1...20 sec. 0...20 sec. 40...70%

PSR72 PSR72 PSR72 PSR85 PSR105 PSR105

- - -

- - -

PSR85 PSR85 PSR105 PSR105

- -

- -

105 A

PSR105 PSR105

-

-

¹ Valid for 50% on time and 50% off time. If other data is required, contact your local ABB office. ² Above 40 °C (104 °F) up to max. 60 °C (140 °F) reduce the rated current with 0.8% per ° C (0.44% per °F). ³ When used at high altitudes, above 1000 meters (3281 ft) up to 4000 meters (13123 ft), de-rate the rated current using the following formula. [ % of Ie = 100 - x-1000 ] x = actual altitude of the softstarter in meter. 150

Data based on an ambient temperature of 40 °C (104 °F), starting current of 4 x I e and ramp time 6 seconds. For more optimized selection or to use PSR for heavy-duty starts, please use the softstarter selection tool.

Made with FlippingBook flipbook maker