SOFTSTARTERS, CONTROL SECTION 9

— PSE Technical data

Technical data

PSE18 ... PSE370

Technical data

PSE18 ... PSE370

Analog output Output signal reference Type of output signal

600 V

Rated insulation voltage U i Rated operational voltage U e Rated control supply voltage U s Rated control circuit voltage U c Starting capacity at I e Number of starts per hour

4...20 mA

208...600 V +10%/-15%

I Amp

100...250 V +10%/-15%, 50/60 Hz ±10%

Scaling

Fixed at 1.2 x I e

Internal 24 V DC 4 x l e for 10 sec.

Control circuit Number of inputs

3 (start, stop, reset of faults)

10¹

Signal indication LED On / Ready

Maximum Altitude Overload capability Overload class Ambient temperature During operation Degree of protection Main circuit Supply and control circuit During storage

4000 m (13123 ft)³

Green flashing / steady Green flashing / steady

Run / TOR Protection

10

Yellow

Fault

Red

-25…+60 °C (-13...+140 °F)² -40…+70 °C (-40...+158 °F)

Protections Electronic overload

Yes (Class 10A, 10, 20, 30)

Locked rotor protection Underload protection Fieldbus connection ABB Fieldbus plug NEW Built-in modbus

Yes Yes

IP00 IP20

Main circuit Built-in bypass Cooling system HMI for settings Display

Yes (option)

Yes

Yes

fan cooled (thermostat controlled)

External keypad Display

LCD type

4 7-segments and icons. Illuminated 2 selection keys and 2 navigation keys

Ambient temperature During operation

Keypad

-25...+60 ° C (-13...+140 °F) -40...+70 ° C (-40...+158 °F)

Main settings Setting current

During storage

Size dependent

Degree of protection

IP66

Ramp time during start Ramp time during stop

1...30 sec 0...30 sec 30...70% 1.5...7 x I e Yes / No Yes / No

¹ Valid for 50% on time and 50% off time. If other data is required, contact your local ABB office. ² Above 40 °C (104 °F) up to max. 60 °C (140 ° F) reduce the rated current with 0.6% per ° C (0.33% per °F). ³ When used at high altitudes, above 1000 meters (3281 ft) up to 4000 meters (13123 ft), de-rate the rated current using the following formula. [ % of I e = 100 - x - 1000 ] x = actual altitude of the softstarter in meters. 150 ⁴ A common voltage needs to be used for all 3 signal relays.

Initial/end voltage

Current limit

Torque control for start Torque control for stop

Kick start

Off, 30...100%

Signal relays Number of signal relays

3

10 000 Time (s)

K2 K3 K1

Run signal

TOR (bypass) signal

Event signal

1000

100-250 V AC/24 V DC⁴

Rated operational voltage U e Rated thermal current I th Rated operational current I e at AC-15 (U e = 250 V) Vibration test According to IEC 60068-2-6:2007

3 A

100

1.5 A

Class 30 Class 20 Class 10 Class 10 A

10

1

0

4

0

6

5

7

8

1

2

3

Current (x I e )

Tripping curves for the integrated electronic overload protection PSE has an integrated electronic overload protection that can be set to four different tripping classes. Above you find a curve for each tripping class in cold state.