INSTOCK® Quick Delivery Lab Outfit Program

Hoods and Enclosures

Features: • Combination Vertical Rising / Horizontal Sliding Sash • Fume Hood is available pre-wired • 24” (61cm) deep clear interior available • Standard 80” (203.2 cm) tall full view sash area Standard Walk-In Fume Hoods - Combination Sash Standard walk-in fume hoods with frameless vertical sash are similar to standard bench style hoods in design and function. The top view pass is clear tempered glass. They provide a clean, bright working environment for most any process or procedure. These hoods are normally used with tall equipment setups where maximum, entrance clearance and full view of a procedure is a priority. • Easy conversion from CAV to VAV use • Chemically resistant white Polyglass liner • Slotted rear baffle for even plenum balance • Chain and sprocket sash mechanism for ease in operation • Can be pre-plumbed with remote control fittings • Other sash configurations and hood styles available upon request • Walk-in hoods are available for shipment in 8-10 weeks • Tempered glass sash with full-length formed steel handle for a neat, clean appearance and streamline air passage • Stainless Steel round collar • Brushed stainless steel cord pass thru

Technical Data: These hoods are UL1805 listed and are tested in accordance to ASHRAE-110. All hoods are pre-wired to a junction box on the roof of the hood with two 120 volt AC 20 amp GFCI receptacles on the side posts, LED light, 20 amp light switch and a duplex for an alarm on the roof. Each front post and interior end liner is punched and capped for up to five (5) remote control service fittings. The left hand post is punched for a second electrical fixture at the top which may be used for a fan switch or other electrical device. The right post is punched and covered for an alarm. Service fittings, fan switch, work floor, cup sink, and alarm must be ordered separately.

100 FPM @ 31.5” Max Sash Opening 858 CFM

100 FPM @ 18” Max Sash Opening

100 FPM @ 50% Horizontal Open

Static Pressure Loss

Static Pressure Loss

Static Pressure Loss

Clear Interior Depth

Duct Size

Cat. No.

Hood Width

F-201-48G5 4’ (121.9 cm) 24” (61 cm)

1:10”

0.39”

501 CFM 0.13”

444 CFM 0.10”

F-201-48G5D30 4’ (121.9 cm) 30” (76 cm)

1:10”

858 CFM

0.39”

501 CFM 0.13”

444 CFM 0.10”

F-201-60G5 5’ (152.4 cm) 24” (61 cm)

1:12” 1128 CFM 0.37”

660 CFM

0.13”

586 CFM

0.10”

F-201-60G5D30 5’ (152.4 cm) 30” (76 cm)

1:12” 1128 CFM 0.37”

660 CFM

0.13”

586 CFM

0.10”

F-201-72G5

6’ (182.9 cm) 24” (61 cm)

1:12” 1399 CFM 0.57”

818 CFM 0.19”

739 CFM 0.16”

F-201-72G5D30 6’ (182.9 cm) 30” (76 cm)

1:12” 1399 CFM 0.57”

818 CFM 0.19”

739 CFM 0.16”

F-201-96G5 8’ (243.8 cm) 24” (61 cm)

2:10” 1941 CFM 0.50”

1135 CFM 0.17”

1035 CFM 0.14”

F-201-96G5D30 8’ (243.8 cm) 30” (76 cm)

2:10” 1941 CFM 0.50”

1135 CFM 0.17”

1035 CFM 0.14”

50% open may be achieved two ways: 1. vertical sash open 14", horizontal panels closed or 2. vertical sash closed, horizontal panels full open