LABORATORY SUMMARY (CONTINUED...)
BUILDING SYSTEMS (CONTINUED...) Power Distribution
There are two services entering interior switchboard cabinets located in each electric room at the rear of the building. One 1600A 480/277 volt -3 phase service with switch gear serving various panel boards. This was the original full building service when the entire building was an office facility. Panels are segregated by lighting and general house power. The second service is a 2000A 277/480 – 3 phase service with distribution panels for lighting and equipment dedicated to the first floor laboratory areas.
There is a central UPS and associated dedicated panel boards serving the main data room.
Emergency Generator A rough in exists for a 200Ampere 480/277 Volt Stand By Generator on the electrical power system.
Lightning Protection Buildings does not include a rooftop lightning protection system.
MECHANICAL AND ELECTRICAL SYSTEMS CAPACITIES
10065 Red Run Boulevard Owings Mills, Maryland Mechanical And Electrical Systems Report
Electric Power KW W/fl2
Air Handler
Area Served
Square Footage Tons
SqFt per Ton
CFM per SqFt
CFM per Ton
Outdoor Air CFM
Outdoor Air
CFM
% VAV or CV
1N North Labs - First Floor
18,330 138 133 24,025 11,250 150 75 22,175
1.3 175 2.0 148
16,355 22,175
68.1 VAV 100.0 VAV
1E
East Labs - First Floor
Totals:
29,580 288 103 46,200
1.56 161
38,530
0.83
2993 51
Typical R & D Lab Facility:
-
-
230
-
1.75 -
-
-
Notes:
1. Typical R & D laboratory facility figures are based on recirculating air with minimal fume hoods. 2. Outdoor air quantity listed can accommodate (36) standard 6 feet fume hoods total.