Connectivity Guide

Flame resistance Cable attributes

Rating

USA

CSA*

FR-00

minimum flame retardancy

UL 62

FT2

FR-01

horizontal flame test one 30 sec. flame application

UL VW-1 (UL 1581)

FT1

FR-02

vertical flame test five 15 sec. flame applications

UL 1581

FT4

FR-03

vertical tray test exposed to flame for 20 min.

UL

FT4-ST1

FR-04

vertical flame & smoke test

UL 1666 flame test for riser cables UL 910 flame test for plenum cables

FR-05

FR-06

FT6

NOTE: Canadian standards are mentioned for reference only. Standards are not represented here as complete equivalents to the US standards, but are referenced due to similarities in requirements. Refer to the individual standards for detailed test procedures and comparable evaluations.

Lapp cables are manufactured to comply with varying degrees of flame resistance requirements. Depending on the application, certain levels of flame resistance are necessary in order to meet specific end-use requirements. Flammability ratings are generally dictated by local or national electrical codes for the specific application.