— ReliaMod™ Main modules Construction details

Construction Details: Main breaker modules 400A-2000A in 1-Phase and 3-Phase models (800A MCB Module Shown below)

Neutral bonding strap, ships in unbonded position

NEMA 3R outdoor enclosure

Factory installed top closure plates

Alternate ground lug location for non-service entrance applications

Tin plated horizontal bus

Flat bus cap (left side)

N

Deep bus cap (right side)

Service ground lugs. Can be relocated to be mounted on the back box in 2 locations for non- service entrance applications

A

B

Adjustable trip unit

C

Incoming line lugs, factory installed

Shear nut on all horizontal bus connections. No torque wrench required

Finger safe line side terminal cover across all incoming line lugs

Alternate ground lug location for non-service entrance applications

Suitable for both bottom or top feed through 1200A

Neutral lugs

RMM3BL8R shown

Construction Details: Main breaker modules 400A-2000A in 1-Phase and 3-Phase models (1600A MCB Module Shown below)

Lifting hooks to assist in installation (can be removed after unit is installed)

Neutral bonding strap, ships in unbonded position

NEMA 3R outdoor enclosure

RELT switch with indicating light to comply with NEC 240.87

Digital LSI adjustable trip unit with RELT

Fuse block for RELT

N

A

Tin plated horizontal bus

Alternate ground lug location for non-service entrance applications Flat bus cap (left side)

B C

Deep bus cap (right side)

Shear nut on all horizontal bus connections. No torque wrench required

Service ground lugs for service entrance applications

Incoming line lugs, factory installed

Neutral lugs

Separate wireway for ground wires

Suitable for bottom feed only in 1400A-2000A models (Also available in top feed only versions as well)

RMM3BB16RL shown

Made with FlippingBook Ebook Creator