BuyLog Flippingbook MAR 2024
METERING, BUYLOG SECTION 2
2-12
— ReliaMod™ Main breaker modules
Main breaker modules: 3-phase 4 wire 208Y/120Vac or 120/240V delta hi-leg, lugs included Main ampere rating kAIC Main breaker frame Breaker trip unit Wire entry Incoming lug sizes per phase & neutral (AWG/kcmil Cu/Al)
Service ground/ equipment ground (AWG/kcmil Cu/Al)
Ordering code RMM3BL4R RMM3BH4R RMM3BL6R RMM3BH6R RMM3BL8R RMM3BH8R RMM3BL10R 3 RMM3BH10R 3 RMM3BL12R 1,3 RMM3BH12R 1,3
400
65 XT5N 100 XT5S 65 XT5N 100 XT5S 65 XT6N 100 XT6S
TMA Top/Bottom
(2) 2/0 - 500
(2) #6-350
600
(2) 2/0 - 500
800
(3) 2/0 - 400
1000
65 XT7S Ekip Dip LS/I
(4) 4/0 - 500
100 XT7H
1200
65 XT7S Ekip Touch LSI
(4) 4/0 - 500
100 XT7H
1400
100
T8V PR332/P LSI
Bottom
Lug landing pad accepts up to 6 wire landings per phase & neutral. Lugs not included, to be provided by others.
RMM3BB14RCLL 1,2
(4) 1/0 - 750 (6) 1/0 - 750 (4) 1/0 - 750 (6) 1/0 - 750
RMM3BB14R 1,5 Coming soon 1,4 RMM3BT14R 1,5 Coming soon 1,4
— 800A MCB Module: RMM3BL8R
Top
1600
Bottom
Lug landing pad accepts up to 6 wire landings per phase & neutral. Lugs not included, to be provided by others.
RMM3BB16RCLL 1,2
(4) 1/0 - 750 (6) 1/0 - 750 (4) 1/0 - 750 (6) 1/0 - 750 (6) 1/0 - 750
RMM3BB16R 1,5 Coming soon 1,4 RMM3BT16R 1,5 Coming soon 1,4 Coming soon 1
Top
2000
Bottom
Top Coming soon 1 Note: Please click on any specific ReliaMod™ ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details. 1RELT included 2Lug landing pad only. Lugs not included, to be provided by others. 3 For larger 600-750 kcmil lugs on an XT7 frame main module, please order RXT7LUGKIT750. This kit will include mechanical lugs to accommodate (3) 500-750 kcmil Cu/Al cables per phase and neutral. 4 This main breaker module comes with (6) cable mechanical lugs per phase and neutral that accept (6) 1/0-750 kcmil Cu/AI cables. It has a larger enclosure than its (4) cable lug counterpart indicated in footnote 5. 5 This main breaker module comes with (4) cable mechanical lugs per phase and neutral that accept (4) 1/0-750 kcmil Cu/Al cables. This unit comes in a smaller enclosure and is more economical than a (6) cable lug model. However, please confirm these lugs meets your project requirements as there is no lug kit to change the lugs in the field once this item ships. If you require lugs that accept 5 or 6 cables per phase and neutral, please select the alternate version of this main module per footnote 4.
— 1600A MCB Module: RMM3BB16RL
Made with FlippingBook Ebook Creator