BuyLog Flippingbook MAR 2024

METERING, BUYLOG SECTION 2

2-14

— ReliaMod™ Main breaker trip unit summary

Below is a summary of the trip units that will come in any main breaker module available in the ReliaMod™ modular metering offering.

ReliaMod™ main breaker module trip unit data Main breaker frame Amperage

Poles

kAIC @ 240V

Trip unit

T8V

1400A-2000A

2 and 3

100

PR332/P LSI 1 Ekip Touch LSI 1

XT7S XT7H XT7S XT7H XT6N XT6S XT5N XT5S

1200A

65

100

1000A

65

Ekip Dip LS/I

100

800A

65

TMA

100

400A-600A

65

TMA

100 1All 1200A and above breaker trip units will automatically be provided with Arc Reduction (RELT) to comply with NEC 240.87

SACE PR332/P LSI Trip Unit in T8V 1400A-2000A Frame Main Breaker Modules (RELT Included) Breaker is LSI only. Ground Fault not included.

Ekip Touch LSI Trip Unit in Tmax XT7 Frame in 1200A Main Breaker Modules (RELT Included)

Ekip Dip LS/I Trip Unit in Tmax XT7 1000A Main Breaker Modules Only

Thermal Magnetic Adjustable (TMA) Trip Unit in Tmax XT5 400A-600A and XT6 800A Frame Main Breaker Modules

Made with FlippingBook Ebook Creator