BuyLog Flippingbook MAR 2024
13-7
BUSWAY, BUYLOG SECTION 13
— ReliaGear™ busway plug-in units
Fusible Plug-in unit horsepower ratings (H class fuses)
Switch
Device Short Circuit
UL
3 phase Maximum HP Rating
Fuse Class
Switch Type
Poles
Rating Rating rms
Cat. No.
(A)
240V AC
480V AC
600V AC
OT30 OT60
OT100F3 OT100F3 OT100F3 OT200U30 OT400U21 OT600U21
3 3 3 3 3 3
30A 60A
10kA 10kA 10kA 10kA 10kA 10kA
H H H H H H
10 20 30 75
20 40 50
30 40 50
OT100 OT200 OT400 OT600
100A 200A 400A 600A
150 250 450
200 350 500
125 200
Ratings are based on NEC Article 430. Horsepower ratings for plugs with NEC fuses are based on one-time fuses having minimum time delay. When time delay fuses are used, the horsepower ratings are maximum for the plug.
Fusible Plug-in unit horsepower ratings (J class fuses)
Switch
Device Short Circuit
UL
3 phase Maximum HP Rating
Fuse Class
Switch Type
Poles
Rating Rating rms
Cat. No.
(A)
240V AC
480V AC
600V AC
OT200 OT200 OT200
OT200U30 OT200U30 OT200U30
3 3 3
30A 60A
200kA 200kA 200kA
R R R
10 20 30
20 40 50
30 40 50
100A
Fusible Plug-in unit horsepower ratings (H class fuses)
Switch
Device Short Circuit
UL
3 phase Maximum HP Rating
Fuse Class
Switch Type
Poles
Rating Rating rms
Cat. No.
(A)
240V AC
480V AC
600V AC
OS30 OS60
OS30FAJ12 OS60GJ30 OS100GJ30 OS200J30 OS400J21 OS600J21
3 3 3 3 3 3
30A 60A
200kA 200kA 200kA 200kA 200kA 200kA
J J J J J J
7,5 15 30 60
15 30 60
20 50 75
OS100 OS200 OS400 OS600
100A 200A 400A 600A
125 250 400
150 350 500
125 200
Made with FlippingBook Ebook Creator