BuyLog Flippingbook MAR 2024
METERING, BUYLOG SECTION 2
2-19
— ReliaMod™ Main lug modules
Main lug modules: 1-phase 3 wire 120/240Vac, lugs included Main ampere rating kAIC Wire entry
Incoming lug sizes per phase & neutral (AWG/kcmil Cu/Al)
Service ground/equipment ground (AWG/kcmil Cu/Al)
Ordering code
400 600 800
100
Top/Bottom
(1) 2/0-600 or (2) 2/0 – 250 and (1) 6-250
(2) #6-350
RMM1L4R RMM1L6R RMM1L8R RMM1L12R RMM1L16R
(2) 250-750 or (4) 3/0 - 250 (3) 250-750 or (6) 3/0-250 (3) 250-750 or (6) 3/0-250 (8) 250-750 or (16) 3/0-250 (8) 250-750 or (16) 3/0 - 250
1200 1600 2000
RMM1L20R Note: If you are using any type of ABB ReliaMod™ main lug module in a service entrance application you will need to have a main disconnect in front of it to comply with NEC 2020 service disconnect barrier and finger safe requirements. ABB ReliaMod™ meter stacks do not have barriers between tenant breakers nor finger safe barriers for the line side of the tenant breakers. Note: Please click on any specific ReliaMod™ ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details.
Main lug modules: 3-phase 4 wire 208Y/120Vac or 120/240V delta hi-leg, lugs included Main ampere rating kAIC Wire entry Incoming lug sizes per phase & neutral (AWG/kcmil Cu/Al)
Service ground/equipment ground (AWG/kcmil Cu/Al)
Ordering code
400 600 800
100
Top/Bottom
(1) 2/0-600 or (2) 2/0 – 250 or (1) 6-250
(2) #6-350
RMM3L4R RMM3L6R RMM3L8R RMM3L12R RMM3L16R
(2) 250-750 or (4) 3/0 - 250 (3) 250-750 or (6) 3/0-250 (3) 250-750 or (6) 3/0-250 (8) 250-750 or (16) 3/0-250 (8) 250-750 or (16) 3/0 - 250
— 600A MLO Module: RMM3L6R
1200 1600 2000
RMM3L20R Note: If you are using any type of ABB ReliaMod™ main lug module in a service entrance application you will need to have a main disconnect in front of it to comply with NEC 2020 service disconnect barrier and finger safe requirements. ABB ReliaMod™ meter stacks do not have barriers between tenant breakers nor finger safe barriers for the line side of the tenant breakers. Note: Please click on any specific ReliaMod™ ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details.
Main lug modules with feed through lugs: 1-phase 3 wire 120/240Vac, lugs included
Service ground/ equipment ground (AWG/kcmil Cu/Al)
Incoming line lug sizes per phase & neutral (AWG/kcmil Cu/Al)
Outgoing load lugs per phase & neutral (AWG/kcmil Cu/Al)
Main ampere rating
Ordering code
kAIC Wire entry
1200 1600 2000
100
Top/ Bottom
(5) 250-750 or (10) 3/0 - 250 (5) 250-750 or (10) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250
(4) #6-350 RMM1L12RFTL
RMM1L16RFTL
RMM1L20RFTL Note: If you are using any type of ABB ReliaMod™ main lug module in a service entrance application you will need to have a main disconnect in front of it to comply with NEC 2020 service disconnect barrier and finger safe requirements. ABB ReliaMod™ meter stacks do not have barriers between tenant breakers nor finger safe barriers for the line side of the tenant breakers. Note: Please click on any specific ReliaMod™ ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details.
— 1200A MLO Feed Through Module: RMM3L12RFTL
Main lug modules with feed through lugs: 3-phase 4 wire 208Y/120Vac or 120/240V delta hi-leg, lugs included
Service ground/ equipment ground (AWG/kcmil Cu/Al)
Incoming line lug sizes per phase & neutral (AWG/kcmil Cu/Al)
Outgoing load lugs per phase & neutral (AWG/kcmil Cu/Al)
Main ampere rating
Ordering code
kAIC Wire entry
1200 1600 2000
100
Top/ Bottom
(5) 250-750 or (10) 3/0 - 250 (5) 250-750 or (10) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250 (8) 250-750 or (16) 3/0 - 250
(4) #6-350 RMM3L12RFTL
RMM3L16RFTL
RMM3L20RFTL Note: If you are using any type of ABB ReliaMod™ main lug module in a service entrance application you will need to have a main disconnect in front of it to comply with NEC 2020 service disconnect barrier and finger safe requirements. ABB ReliaMod™ meter stacks do not have barriers between tenant breakers nor finger safe barriers for the line side of the tenant breakers. Note: Please click on any specific ReliaMod™ ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details.
Made with FlippingBook Ebook Creator