Control Catalog
NEMA Full Voltage Power Devices NEMA Rated Full Voltage Starters - Magnetic
Section 1
CR324X Solid State Overload Relays For Panel Mounting 3-Pole, 600 VAC
Tripping Time (sec.) vs. Multiples of F.L .A. for GE CR324X overload, cold state
Fusible Combination Starter Short Circuit Ratings NEMA Rated Full Voltage Starters Fusible Combination Starters & CR324X Solid-State Overload Relays
Typical 3-Phase Diagram
Maximum Symmetrical rms Amperes
NEMA Size
Fuse Type
0-3
H, K H, K
5,000 at 600 V
4, 5
10,000 at 600 V
0-4
J
100,000 at 600 V
0-4
RK1, RK5
65,000 at 480 V
5
J, RK1, RK5
100,000 at 600 V
6
J, L, RK1, RK5
100,000 at 600 V
CR324X Circuit Breaker Combination Starter Short Circuit Ratings
Circuit Breaker Combination Starters & CR324X Solid-State Overload Relays
Maximum Symmetrical rms Amperes
Breaker Type
Rating
NEMA Size
240 Volts
480 Volts
600 Volts
— — — —
— — — —
15-50
0
5,000
15-70
1
5,000
TEB
15-100
2
5,000
25-150
3
5,000
3-15
0
25,000
25,000
5,000
3-15
1
25,000
25,000
5,000
15-50
2
25,000
25,000
5,000
TEC Mag-Break® Breaker
30-100
3
25,000
25,000
5,000
50-150
4
25,000
25,000
5,000
3-30
0
100,000
100,000
100,000
3-50
1
100,000
100,000
100,000
TEC/TECL
15-50
2
100,000
100,000
100,000
30-100
3
100,000
100,000
100,000
50-100
4
100,000
100,000
100,000
15-50
0
5,000
5,000
5,000
15-30
1
25,000
25,000
5,000
35-70
1
5,000
5,000
5,000
TED
15-50
2
25,000
25,000
5,000
60-100
2
5,000
5,000
5,000
25-100
3
25,000
25,000
5,000
110-150
3
5,000
5,000
5,000
70-225
4
25,000
25,000
18,000
70-225
4
25,000
25,000
18,000
TFJ, TFK & TFC THFK TJJ, TJK & TJC THJK
225-600
5
10,000
10,000
10,000
225-400
5
35,000
35,000
25,000
450-600
5
35,000
35,000
25,000
300-800
6
42,000
42,000
22,000
TKM, TKC THKMB TB6, TBC
300-800
6
65,000
35,000
25,000
300-800
6
65,000
65,000
42,000
Rev. 4/16 Prices and data subject to change without notice
Control Catalog
www.geindustrial.com
1-162