IVSI-H-3P-S-X468 Catalog

RUGGED INDUSTRIAL PRODUCTS

I VSI- H -3P- S*-X468 SERIES - 500 to 3000 kVA - THREE PHASE

TECHNICAL SPECIFICATION

Technology:

Magnetic Induction Design - Brushless Oil Immersed

Surge Suppression:

TVSS - Protects loads against high-energy Spikes and Transient Voltages.

Total Harmonic Distortion:

Less than 1%

Input Voltage Swing Variant Options Available: (S*)

Model / Accuracy

± 1.5%

± 5%

± 3%

-12% +13%

-14% +16%

S10

± 10%

Independent Phase Control:

Maintains each phase voltage stable irrespective of load unbalance, even up to 100% load unbalance. Temperature range –15 to 45 °C. Derate by 2% for each additional °C Up to max 60 °C . Suitable for indoor tropical use 95% RH (non- condensing). Maximum altitude 1000m. Derate by 2.5% for each additional 500m.

-17% +18%

-19% +21%

S15

± 15%

-22% +23%

-24% +26%

S20

- ± 20%

Environment:

-27% +28%

-29% +31%

S25

-± 25%

-32% +33%

-34% +36%

S30

-± 30%

Presettable for any voltage between 440/254V, 460/265V, or 480/277V - Customer to Specify, Three Phase, 4 Wire. ( 3 Phase + Neutral) 380/220V, 400/230V & 415/240V models available. The permissible input voltage swing is relative to the preset output voltage. Three Phase, 4 Wire ( 3 Phase + Neutral). Other swing options available to special quotation / order.

Insulation Oil:

Uninhibited Transformer Oil conforming to BS EN 60296 (2004).

Output Voltage:

Construction:

Enclosures to IP20 (NEMA 1 Style) - BS EN 60529.

Paint Colour:

RAL 7032 (Grey - Epoxy Powder Coating)

EMC Conformance:

Complies with BS EN 55022 and the relevant parts of the BS EN 61000 series of standards.

CE Conformity:

CE Marked - being fully compliant with European Union Directives 2004/108/EC (The EMC Directive) and 2006/95/EC (The Low Voltage Directive).

Output Voltage Accuracy:

± 1.5%, ± 3% or ± 5 % - auto selection based on input voltage swing.

Standard Warranty:

Two Years / 24 Months from date of supply

Frequency:

47 - 65Hz

Loss of Phase & Phase Reversal Alarms Over Temperature Alarm Over Voltage & Low Voltage Alarms Voltmeter / Selector Switch Ammeter / Selector Switch No-Volt Free Contacts (N.C & N.O) Lightning Surge Arrestors Oil Pressure Safety Release Valve Supplied Oil Filled System Switch Board with - Input Circuit Breaker, Output Circuit Breaker, Manual Maintenance Bypass Switch & Metering & Interlocking Protection

Standard Features:

Response Time:

<1.5ms

Correction Time:

A 10% supply variation will be corrected to within 2.5% in typically 0.6 to 1 second - dependent on the selected permissible input voltage swing and system rating.

Efficiency:

≥ 97%

Power Factor:

Any lagging to 0.95 leading

Optional Main System Switch Board (MSB):

Surge Ratings:

10 x max. current rating for 2 seconds 3 x max. current rating for 1 minute 2 x max. current rating for 2 minutes

(3 Pole as standard with 4 Pole option)

PRODUCT SELECTION TABLE

Model - IVSI-1500H-3P-S15 - 1500 kVA

Max Rating (Amps per Phase)

Rating kVA

Dimensions & Weights

Model

@ 440V @ 460V

@ 480V

500

IVSI-500H-3P- S *-X468

655

627

601

750

IVSI-750H-3P- S *-X468

983

941

901

Dimensions & Weights available on Request - according to the S* Swing Model Variant required.

1000

IVSI-1000H-3P- S *-X468

1311

1254

1202

1250

IVSI-1250H-3P- S *-X468

1639

1568

1503

1500

IVSI-1500H-3P- S *-X468

1967

1882

1803

2000

IVSI-2000H-3P- S *-X468

2623

2509

2404

2500

IVSI-2500H-3P- S *-X468

3279

3137

3006

3000

IVSI-3000H-3P- S *-X468

3935

3764

3607

Note: Alternative voltage options available to order / individual request.

Typical Outline Drawing

Model: IVS-2000H-3P-S30 - 2000 kVA

Optional - Main Switch Board with Bypass

Copyright 2012 © Ashley-Edison (UK) reserve the right tochange any or all the specifications indicated or implied without prior notice. E&EO.

IVSI-H-3P-X468 SEPT2012-V2

www.AshleyEdison.com

Made with