asecos Catalogue 2013/14 - page 276-277

Recirculating air filter system – avoid complex wall
and ceiling openings and expensive exhaust air ducts
• high flexibility in choosing the installation location
• active personal protection through safe capture of
harmful vapours with retention in the filter system
• very low noise, only approx. 39 dB (A)
• ATEX complient: CE II 3/-G Ex ic nA IIB T4 Gc
• housing made of sheet-steel plastic laminated
• with multistage filter system and power cord
• incl. VDE tested extraction and filter monitoring
• optical and acoustical alarm including potential-free
alarm contact
• dimensions W x D x H (mm): 305 x 555 x 210
The plug-in recirculating air filter system UFA.20.30 is
capable of retaining solvent vapours (hydrocarbons)
permanently up to a filter saturation of more than
99,999 %, under normal operating conditions as well
as for a simulated accident in the safety storage cabinet
A special version of the recirculating air filter system is
also available to meet the pressure and volumetric flow
conditions inside XL-LINE Drum Cabinets (further details
see page 184-189)
The asecos recirculating air filter
system – successfully tested and
certified by the testing institute
Load capacity of the voltage-free alarm contact
Maximum nominal voltage: AC 230 V ~
Maximum nominal voltage: DC 48 V
Maximum switching current:
1A
Technical data
Motor rating
kW
0.03
Nominal voltage
V
230
Frequency
Hz
50
Input current
A
0.13
Noise level
dB (A)
39
Revolutions
rpm
2450
Activated carbon filter weight
(incl. filling 3500 g)
kg
4.2
Volumetric flow
(mounted on the cabinet)
ca. 25 m
3
/h
Recirculating air filter system UFA.20.30
Order No. 25099
n
Recirculating air filter system according to
2006/95/EG
(Low Voltage directive)
marking CE II 3/-G Ex ic nA IIB T4 Gc
conform with the EMC Directive
RL 2004/108/EG and RL 94/9/EG
(ATEX Directive)
Recirculating air filter system UFA.20.30-AUS for underbench
cabinets
Safe capturing of escaping vapours at the point where they
are released or produced
The recirculating air filter system UFA.20.30-AUS was especially
designed for the pressure conditions and volumetric flows of safety
storage cabinets with a small internal volume. It can be installed on
a wall bracket (illustration on right) or in a convenient housing unit
(illustration below).
Option 1:
wall bracket for
installation on a wall
Order No. 23458
n
Option 2:
Recirculating air filter system UFA.20.30-AUS
with housing unit (without underbench cabinet)
Order No. 27318
n
Article
Order No.
Recirculating air filter system UFA.20.30
25099
n
Recirculating air filter system UFA.20.30-XL
for drum cabinets
27887
n
Accessories
Replacement filter for UFA.20.30
24212
n
Adapter for drum cabinets
15776
n
Article
Order No.
Recirculating air filter system UFA.20.30-AUS
27144
n
Accessories
Wall bracket, suitable for installation on a wall for UFA.20.30-AUS
23458
n
Article
Recirculating air filter system UFA.20.30-AUS with housing unit for asecos underbench cabinets
27318
n
Accessories for both articles
Replacement filter for UFA.20.30-AUS
24212
n
UFA-LINE
277
Ready for dispatch within
n
2 days
276
Ready for dispatch within
n
2 days
UFA-LINE