10.6 Unusual Noises Due to Compressor

1. Suction pressure less than about 5 psig can cause unusual noise. Charge refrigerant to proper amount and test by applying heat to evaporator to increase suction pressure. 2. Clutch bearing--See clutch Inspection in section 10.4 3. Oil level--insufficient oil can cause unusual noise. See Oil Level Check Procedure in Section 10.2. 4. Valve Noise--test for valve plate assembly failure per Valve Plate Test Procedure in Section 10.7.

10.7 Valve Plate Test

1. Suction or discharge valve breakage will cause a clacking sound at idle. 2. If head gasket failure occurs, discharge pressure will be low and suction pressure will be high at idle. 3. Valve and gasket condition can be checked as follows: · Connect gauge set to suction and discharge service valves. · Run compressor for 5 minutes at idle and stop. · Observe time for discharge pressure and suction pressure to equalize. If less than 2 minutes, in a TVX system, a valve or gasket may be damaged. CCOT systems will equalize more quickly.