CanadianConnectors (CA05041E )

EHV Deadend, 2-Bundle Conductor Double Insulator 30k lb Assembly, 230kV - 345kV

ASSEMBLY TAD22CVN

7.25

3.50

Section Length

6.16

24.00 3.06

2.47

2.28

18.00

1

2

1

3

8

7

6

4

5

1.25

Ø.88

Base Assembly Bill of Material

Item Part Number

Description

Quantity

Material

UBS lb 60,000 60,000 60,000

1 2 3 4 5 6 7 8

AS50WBNKCVN HOO5024CVN YPD60183771CVN

Anchor Shackle

2 1 1 2 2 1 2 2

Forged Steel Forged Steel

Oval Eye Ext. Link (24")

Yoke Plate

Cut Steel Polymer

See Chart SYC133SN

Insulator, ANSI 52-5

Socket Y-Clevis

Forged Steel

30,000 30,000 30,000

YPR30187221CVN AS25LBNKSNCVN

Yoke Plate

Cut Steel

Anchor Shackle

Forged Steel Aluminum

See Note 1

Compression Deadend w/Terminal

Full Tension

Typical Insulator Selection

Line Voltage (kV)

Quadri*Sil® Part Number

Section Length Inches

SML lb

Corona Ring

230

S030073S201A

85.1

30,000

8" Line End

345

S0301O3S201B

115.3

30,000

12" Line End

NOTE: For quoting/ordering instructions, see Assemblies section. (1) See Uni-Grip Compression Deadends section for standard conductor compression deadend options.

©2017 Hubbell Incorporated | hubbellpowersystems.com

H-42

Made with FlippingBook flipbook maker