CanadianConnectors (CA05041E )

Deadends— Bolted Quadrant Strain Clamp Aluminum ( continued )

L

L

PD

K Dia

W

ia

Groove Angle 60º r An l º

13 / 16 Bolted Deadends containing the ‘CVN’ suffix will come supplied with a Charpy Level 1 rated (20 Joules at -20 degrees C) load bearing clevis bolt and hardware galvanized per CSA G164. “ 3 / 4 “ 7 / 8 “ 5 / 8 “ 13 / 16 3 / 4 7 / 8 5 / 8 “

H

C

2 1 / 2

2 1 / 2

3 3 / 8

3 / 8

2 1 / 16

1 / 16

2 1 / 2

1 / 2

Socket Type SA c t

Clevis Type CA l is

Socket Type SA1417 c t

Clevis Type CA1517033 l is

Product Data and Conductor Size

Fitting

Clamping Range

U-Bolts

Ultimate Strength lb (kN)

Approx Weight Each lb (kg)

Catalog Number

Size Inches (mm) 1/2 (12.70)

Catalog Number

Type

ACSR

Aluminum Inches (mm)

No

#4-6/1 to 266.8-26/7 #2-7/1 to 397.5-18/1 #3/0-6/1 to 556-26/7 #3/0-6/1 to 954-54/7 336.4-26/7 to 1272-54/19

#4-7 str to 300-37 str #1-7 str to 397.5-37 str 3/0-19 str to 650-61 str 4/0-19 str to 1033.5-61 str 397.5-19 str to 1431-61 str 1,100-91 str to 1,700-127 str 1,272-61 str to 2,500-127 str

.20-.64 (5.08-16.26)

SD57NBNKCVN None

SA04CVN

15,000 (67)

3

3.2 (1.45)

SD70NBNKCVN SD70SBNKCVN

None Socket

.30-.75 (7.62-19.05)

1/2 (12.70)

4.7 (2.14) 6.0 (2.72)

— SA06CVN

20,000 (89)

4

.46-.94 (10.16-23.88)

1/2 (12.70)

SD86NBNKCVN None

25,000 (111)

4

5.4 (2.45)

SD112NBNKCVN SD112SBNKCVN

None Socket

.50-1.20 (12.80-30.48)

30,000 (133) 30,000 (133)

1/2 (12.70)

8.4 (3.81) 9.9 (4.5)

— SA1013CVN

5

SD130NBNKCVN SD130SBNKCVN

None Socket

.70-1.39 (17.78-35.30)

35,000 (156) 30,000 (133)

5/8 (15.88)

13.2 (6.00) 15.3 (6.95)

— SA1013CVN

5

1,033.5 (36/1) to 1510.5 (54/19) 1,192.5 (45/7) to 2,156 (84/19)

1.18-1.55 (29.97-38.61)

5/8 (15.88)

SD155NBNKCVN None

35,000 (156)

5

15.5 (7.00)

1.30-1.85 (33.02-46.99)

5/8 (15.88)

SD185NBNKCVN None

50,000 (222)

5

21.0 (9.53)

NOTE: Sag eye ultimate strength is 60% of clamp strength without fitting. Rated slip strength as a percentage of conductor RBS varies with conductor type, size and stranding. Minimum slip strength rating on standard strength conductors is 40% RBS (partial tension). For most standard strength conductors, minimum slip strength of this clamp series is 60% RBS (normal tension). Consult factory for slip strength test data on specific clamp and conductor combinations. Recommended torque on U-bolts: 1/2” — 480 in- lb, 5/8 ” — 720 in-lb. For corona-free applications on EHV lines, add suffix “CRF” to catalog number. Example SD130NCRF.

©2017 Hubbell Incorporated | hubbellpowersystems.com

C-2

Made with FlippingBook flipbook maker