WCA November 2019

Corrosiveness of the combustion gases (absence of halogen) Determination of Acidity IEC 60754-1/EN 50267-2-1 Test set-up : A sample of between 0.5g and 1g is heated in a tube. The resulting gases are dissolved and tested for their halogen content. Test apparatus according to EN 50267-1. Flame temperature : 800°C ±10°C Test duration : 40 ±5 minutes in total, with at least 20 minutes at the maximum temperature. Compliance criterion : The amount of halogen acid is expressed as mg of hydrochloric acid per gram mass of sample.

materials that contain no halogens, and the other for those that include a high percentage of halogens, with the most common being chlorine, fluorine and bromine. The below table illustrates the halogen content in typical insulation and jacket materials:

Material

Halogen content weight (%)

PE (Polyethylene)

<0.02 <0.02 <0.02 <0.02 13-26 14-28 22-29 62-78

XLPE

EPR

PU (Polyurethane)

CSPE (Chorosulphonated Polyethylene) CPE (Chlorinated Polyethylene)

PVC

Furnace

FEP (Fluorinated Ethylene Propylene)

Wash bottles

Synth air

Halogen-free cable tests Measurement of smoke density of cables IEC 61034-2 / EN 61034-2

Temperature sensor

Electrical heating oven

Test set-up : A cable specimen is burnt in a closed chamber using a flammable liquid. The light transmittance of the resulting smoke is measured optically. Test apparatus according to IEC/EN 61034-1. Flame temperature : Determined by the quantity and

Why use Alfanar LSHF cables and wires? • Green, safe and healthy : They offer the added benefit of being more environmentally friendly • Halogen-free products : They eliminate the threat of forming caustic acids (such as hydrochloric acid) and contribute to less corrosion damage to equipment near the fire • No emission of toxic gases : They eliminate the threat of inhaling toxic gases and reduce damage to the human respiratory system • Reduction of smoke emission to a minimum : No release of dense smoke that impairs visibility of the fire exit routes and hampers rescue operations • Resistant to ignition : It takes much more time than traditional cables to catch fire, which facilitates the evacuation procedure • Reduction of flame propagation : Their excellent flame-retardant property prevents the fire from spreading • Easy to install : LSHF jackets have a lower coefficient of friction than some non-LSHF jackets, which can make cable installation easier

composition of the fuel. Test duration : 40 minutes.

Compliance criterion : The smoke must transmit the light at the end of the test duration, as stated in individual specifications. The recommendation of light transmission is 60 per cent minimum.

Circulating air protection

Optical receptor