MVF/MVP M echanically S eamed V ertical Leg F lat M echanically S eamed V ertical Leg P encil-rib

®

ERECTION SEQUENCE

STEP 5

(2)#12-14 X 1 1/4" FASTENERS INTO EACH CLIP AT BUILDING LINE

CLIP INSTALLATION

NOTE Do not stand in flat of panel during clip installation. This will affect panel modularity.

MVF/MVP panel clips require (2) fasteners per clip. See Roof Panel Plan for clip and fastener type. Hook the panel clip onto male leg of panel. Hold end of clip up to keep it engaged onto male leg and rotate the clip base down to completely engage clip onto male leg. Install panel clips at each purlin. A clip MUST be installed on ALL purlins. Ensure that clips are installed so that there are no gaps from the face of the high rib to the face of the panel clip. The first run of clips at building line require (2)#12-14 x 1 1/4” fasteners, wall color, to be run through the panel into the clips.

PANEL CLIP (REFER TO ROOF PANEL PLAN FOR CLIP TYPE AND FASTENERS)

INSTALL CLIP SO THAT IT IS PARALLEL WITH THE RIB OF THE PANEL - NO GAP .

Install the clip so that there is no gap between the clip and the vertical leg of the panel. This will help maintain panel modularity.

CAUTION The panel clip has factory applied mastic in the upper lip. This mastic is compressed when the clip is rotated in place. If, for some reason, a clip must be removed, a new clip must be used.

CORRECT

INCORRECT

Version 2.0

SUBJECT TO CHANGE WITHOUT NOTICE

MVF/MVP-27