TPI May 2013

valves , f i t t ings , f langes and connectors

Best practices for installation of safety valves By Kelly Paffel, Swagelok Company

nectors

One of the most critical automatic safety devices in a steam system is the safety valve. The safety valve provides a protective measure for lives, equipment and property from potentially dangerous levels of temperature and forces caused by excessive steam pressure in a system. Safety valves are required by code and insurers. Therefore, it is important to have good, up-to-date records of all safety valves in the steam system. With today’s readily available technology, a database should be developed containing all the relative information of all safety devices in a facility. The safety valve database should be reviewed on a periodic basis depending on plant standards, insurance company recommendations, and the local, state or federal government requirements. The code that establishes the requirements for safety valves is governed by the American Society of Mechanical Engineers (ASME). Through its committees, ASME has published and continues to update the Boiler and Pressure Vessel codes for safety valves. It is the responsibility of

New installation of the vent pipe – proper supports are being installed

The set point for the safety valve is suggested to provide a differential between operating and set steam pressures of at least 20 per cent. When considering a safety valve downstream of a steam pressure control valve, the total capacity of the safety valve at the set point must exceed the steam control valve’s maximum flow capacity (largest orifice available) if the steam valve were to fail open. The inlet steam pressure to the valve must be calculated at the maximum safety valve setting of the steam supply source, not the nominal operating pressure. It is important not to oversize a safety valve. Bigger is not better in this case, because a larger than required valve could cause chatter, leakage and premature failure. Many times, a single safety valve is not possible due to high capacity, physical limitations or economic considerations. An acceptable alternative method is to employ multiple safety valves on the same system. The valves should be of the same set point, and the capacities must be equal to or greater than the rating of the equipment.

plant personnel, primarily the steam team, to know which codes apply to the different parts of the steam system. In the United States the major considerations for safety valves are proper sizing, followed by correct installation. A partial listing of sizing and installation highlights is listed below.

A proper safety valve installation with a drip pan elbow, and proper drain lines off the safety valve and drip pan elbow

54

Tube Products International May 2013

www.read-tpi.com

Made with