NEMA FULL VOLTAGE POWER DEVICES, CONTROL SECTION 1
— CR487 mag-break magnetic starters Nonreversing, combination, mag-break circuit breaker type
Part number configuration Valid for NEMA sizes 0–4
— Step 7 (digit 15) select push button/selector switch
— Step 8 (digit 16) select pilot device
Push button/selector switch — heavy duty
Code
Pilot light (heavy duty) type
Color — functionality Code
None
A
None
A 1 2
Start/stop push button
J
LED lights
Red–across coil Green–across coil
H and-off-auto (HOA) selector switch
L
Off-on selector switch
M
HOA SS and start push button
S
Red–thru NO aux contact Green–thru NC aux contact
3 7 4 7 5 8 6 7 7 7
Keyed HOA SS, key removal center pos.
N
Red–thru NO aux contact and green–thru NC aux contact
Red–across coil and green–thru NC aux contact
Red–across coil and green–thru NC aux contact and unwired amber
Push-to-test lights
Red–across coil Green–across coil
R S
Red–thru NO aux contact Green–thru NC aux contact
C 7 D 7 E 8 V 7 Y 7
Red–thru NO aux contact and green–thru NC aux contact
Red–across coil and green–thru NC aux contact
Red–across coil and green–thru NC aux contact and unwired amber
7 Maximum of 3 Aux contacts may be added to sizes 0 and 1. 8 Maximum of 2 Aux contacts may be added to sizes 0 and 1. Maximum of 3 Aux contacts may be added to sizes 2-4. Note: Auxiliary contacts wired as part of pilot light selection are in addition to the auxiliary contacts selected from step 5 (digit 13) table, page 1-57, which are for customer/field connections.
— Step 9 (digit 17) select control options
Device
Code
None
A
1 relay, 2NO-2NC, 24/120 V coil - unwired
B 2,9 C 2,9
2 relays, 24/120 V coil - unwired
DIN rail - for customer use
D 2 E 2
12 point terminal strip - unwired (12 PT strip)
Space heater w/ NC contact
H 2,10 J 2,9 K 2,9 L 2,10
1 relay + 12 PT strip 2 relays + 12 PT strip
DIN rail + 12 PT strip + space heater 2 relays + 12 PT strip + space heater
M 2,9,10
Time delay on relay, 24/120 V coil - unwired (TD) Time delay off relay, 24/120 V coil - unwired (TD)
N 2,9 P 2,9 R 2,9 S 2,9
12 PT strip + TD on 12 PT strip + TD off
12 PT strip + space heater + TD on 12 PT strip + space heater + TD off
T 2,9,10 U 2,9,10
2 Requires oversized enclosure for NEMA sizes 0-2. Select proper NEMA size and enclosure type from step 1 (digits 1-7) table, page 1-55. 9 Relay/timer coil voltage is equivalent to CPT secondary voltage. Requires minimum 100 extra VA CPT option. 10 Maximum number of auxiliary contacts shall be reduced by 1.
General note: If selecting factory installed and wired operator devices (Push Buttons, Selector Switches, and/or Pilot Lights) control circuit fusing, a control power transformer, or 24 V/120 V separate sourced control is required, regardless of protective device rating.
Made with FlippingBook Online newsletter creator