GE Products BuyLog Smart Catalog

Molded Case Circuit Breakers Record Plus ™ FG 600

Section 6

Interrupting Ratings

UL Listed Interrupting Ratings - EN 60947-2 Interrupting Ratings - rms Symmetrical Amperes (in Thousands) AC Voltage rms Symmetrical Amperes (in Thousands)

Type Ampere Rating Max Voltage No. Poles 240 480 600 240 400-415 690 FGN 250-600A 600VAC 2 150 65 25 – – – 3 150 65 25 85 50 10 FGH 250-600A 600VAC 2 200 100 35 – – – 3 200 100 35 100 80 22 FGL 1 250-600A 600VAC 2 200 150 42 – – – 3 200 150 42 200 150 40 FGP 1 250-600A 600VAC 2 200 200 65 – – – 3 200 200 65 – – – 1 Not suitable for reverse feed. Product Number Structure F G N 3 6 D B 250L F

Connection Configuration

Family F = Record Plus

Frame Size G = 600A

Interruption Rating (@480VAC) N = 65kA

Poles 2 = 2-Pole

Voltage 6 = 600VAC

Trip Unit Type D = PremEon S 2 K = SMR2

Trip Unit Protection A = SMR2 standard Z = SMR2 with ZSI B = LI C = LI 400 Hz G = LIG w/Ground Fault M = Mag-Only MCP P = Mag-Only MCP w/Ground Fault

Trip Unit/Frame Amps 0250 = 250A SMR2 0400 = 400A SMR2 0600 = 600A SMR2 250L = 250A PremEon 400L = 400A PremEon 600M = 600A PremEon

R0 = Standard No Lugs R1 = Line and Load Lugs 3

in 3-Pole Frame

3 = 3-Pole

R2 = Load Lugs 3 R3 = Line Lugs 3

H = 100kA L = 150kA P = 200kA

F = PremEon Standard No Lugs

2 Requires tamper-resistant Torx T15 tool for adjustment 3 Lugs included but not installed

PremEon S FG Breakers and MCP's equipped with the PremEon S trip unit use an adjustment knob to set the Amp rating (LT Pickup). The maximum Amp rating of the breaker frame is shown in the "Current Sensor" column below. The available Amp rating settings (LT Pickup values), by sensor, are as follows:

Current Sensor (A)

Amp Settings (LT Pickup)

250 400 600

80, 90, 100, 110, 125, 135, 150, 165, 175, 190, 200, 215, 225, 240, 250 125, 150, 175, 180, 200, 225, 240, 250, 275, 300, 325, 340, 350, 375, 400 175, 200, 225, 250, 300, 325, 350, 400, 425, 450, 475, 500, 550, 575, 600

LI Trip Unit (With Tracking Short-Time) 2-Pole Record Plus FG Breakers 65kAIC @480 Vac

100kAIC @480 Vac Product Number FGH26DB250LF FGH26DB400LF FGH26DB600MF 100kAIC @480 Vac Product Number FGH36DB250LF FGH36DB400LF FGH36DB600MF 100kAIC @480 Vac Product Number FGH26DG250LF FGH26DG400LF FGH26DG600MF 100kAIC @480 Vac Product Number FGH36DG250LF FGH36DG400LF FGH36DG600MF 100kAIC @480 Vac Product Number FGH26DC250LF FGH26DC400LF FGH26DC600MF 100kAIC @480 Vac Product Number FGH36DC250LF FGH36DC400LF FGH36DC600MF

150kAIC @480 Vac Product Number

200kAIC @480 Vac Product Number FGP26DB250LF FGP26DB400LF FGP26DB600MF 200kAIC @480 Vac Product Number FGP36DB250LF FGP36DB400LF FGP36DB600MF 200kAIC @480 Vac Product Number FGP26DG250LF FGP26DG400LF FGP26DG600MF 200kAIC @480 Vac Product Number FGP36DG250LF FGP36DG400LF FGP36DG600MF 200kAIC @480 Vac Product Number FGP26DC250LF FGP26DC400LF FGP26DC600MF 200kAIC @480 Vac Product Number FGP36DC250LF FGP36DC400LF FGP36DC600MF

Current Sensor (A)

Product Number FGN26DB250LF FGN26DB400LF FGN26DB600MF 65kAIC @480 Vac Product Number FGN36DB250LF FGN36DB400LF FGN36DB600MF Product Number FGN26DG250LF FGN26DG400LF FGN26DG600MF 65kAIC @480 Vac Product Number FGN36DG250LF FGN36DG400LF FGN36DG600MF Product Number FGN26DC250LF FGN26DC400LF FGN26DC600MF 65kAIC @480 Vac Product Number FGN36DC250LF FGN36DC400LF FGN36DC600MF

250 400 600

FGL26DB250LF FGL26DB400LF FGL26DB600MF

3-Pole Record Plus FG Breakers

150kAIC @480 Vac Product Number

Current Sensor (A)

250 400 600

FGL36DB250LF FGL36DB400LF FGL36DB600MF

LIG Trip Unit (With Tracking Short-Time) 2-Pole Record Plus FG Breakers 65kAIC @480 Vac

150kAIC @480 Vac Product Number FGL26DG250LF FGL26DG400LF FGL26DG600MF 150kAIC @480 Vac Product Number FGL36DG250LF FGL36DG400LF FGL36DG600MF

Current Sensor (A)

250 400 600

3-Pole Record Plus FG Breakers

Current Sensor (A)

250 400 600

400 Hz LI Trip Unit (With Tracking Short-Time) 4 2-Pole Record Plus FG Breakers 65kAIC @480 Vac

150kAIC @480 Vac Product Number

Current Sensor (A)

250 400 600

FGL26DC250LF FGL26DC400LF FGL26DC600MF

3-Pole Record Plus FG Breakers

150kAIC @480 Vac Product Number

Current Sensor (A)

250 400 600

FGL36DC250LF FGL36DC400LF FGL36DC600MF

4 400 Hz FG breakers require de-rating and are not UL listed.

Rev. 1/19 Data subject to change without notice

GE Products BuyLog

go.abb/industrial

6-84