The drawout mechanism allows the breaker to be racked in four distinct positions (CONNECTED, TEST, DISCONNECTED, WITHDRAWN). Choice of whether shutters are needed are based in the order option 2nd disconnect Block B (GSDWCR). EntelliGuard ™ G Cassette Product Number Structure 16 M 2 5 A

G Digit 1 Digit 2 Digit 3,4 Digit 5

Digit 6 Digit 7

Circuit Breaker Cassette Family G=EntelliGuard ™ G Breaker/Switch

Shutters Shutter and Shutter Lock- Factory Installed

Breaker Switch Type ANSI / UL1066 Circuit Breaker

Number of Poles

OEM Cassette - 3 Pole

Current Rating 1600 A

Cassette AIC Rating Envelope 2, 400-3200 Envelope 3, 4000-5000

Digit 1 Circuit Breaker Cassette Family Devices Series/Line Code EntelliGuard ™ G Breaker/Switch G

Digit 3 and 4 Current Rating Current Rating (A) Circuit Breaker ANSI UL489 800 08 08 1600 16 16 2000 20 20 3000 - 30 3200 32 - 5000 50 - 6000 - 60 NOTE: Select Current Rating equal to or the next higher of the Circuit Breaker or Switch Current Rating

Digit 2 Breaker Switch Type Cassette Type,

Envelope 1 Envelope 2 & 3

Secondary Mounting

Side

Top Top

ANSI/UL1066

A

N A

Circuit Breaker UL489 Circuit Breaker ANSI Non-auto CB ( ANSI Switch) UL489 Non-auto CB

B

U B

C

M C

D

S D

(UL Switch)

—Top = Top Mounted Secondary Disconnects (TSD). —Side = Side Mounted Secondary Disconnects (SSD). (Available on Envelope 1 only). —N, U, M, S characters are for Envelope 1 only with top mounted secondary disconnects (TSD). —When ordering codes A and B, Side Secondary Disconnects (SSD) are supplied as standard on Envelope 1. —Codes N and U, are not valid for Envelopes 2 and 3. —Envelope 1 (Type N and H, Circuit Breaker and Switches, 800A - 2000A). NOTE: Side Secondary Disconnects are specifically intended for 5-High ("high density") equipment designs With Side Mounted Disconnects (SSD), EntelliGuard ™ Circuit Breakers Auxiliary Switches cannot be 8NO+8NC (Power Rated) or Aux. Switch, 4NO/4NC (Power Rated) + 4NO/4NC (High Fidelity)