Low Voltage Power & Insulated Case Circuit Breakers Section 8

EntelliGuard ™ G Low Voltage Power Circuit Breakers EntelliGuard ™ G Accessories

Status Indication Switch (Coil Signaling Contact) A plug-in module is available to provide status indication via the secondary disconnects and trip unit. Coil Signaling Contacts are available for closing coils, shunt trips and under voltage releases. Contact is mounted on top of the Accessory Device. One of the low signal (Hi-Fi) contacts is always wired to the trip unit.

Status Indication Switch

Type and

Product

Configuration Rating Voltage

Amps Number

AC 120Vac

6 6

1 Power rated + AC 250Vac 1 Low signal (Hi-Fi) DC 120Vac (1NO contact each) DC 250Vac

0.5

GCSP1R

0.25

AC 125Vac DC 30Vdc

0.1 0.1

2 Low signal (Hi-Fi) (1NO contact each)

AC 125Vac

0.1

GCSP2R

Status Indication Switch

Power Nominal Consumption Control Voltage Product Number 24Vdc GUVT024DR DC: 350W, 30Vdc GUVT030DR 2W (sealed) 40Vdc; 48Vac/dc GUVT048R 60 - 72Vdc GUVT060DR AC: 350W 110Vdc/130Vdc; 120Vac GUVT120R (inrush), 208Vac GUVT208AR 20W (sealed) 220Vdc; 240Vac GUVT240R 250Vdc; 277Vac GUVT277R Duty Cycle = 2/min. Under Voltage Release (UVR) with Fixed Time Delay The UVR instantaneously activates the circuit breaker trip mechanism when the source voltage drops below the low voltage threshold. The UVR is also a simple, field installable device.

Under Voltage Release

Inrush = 350VA (AC), 350W (DC) Holding = 60VA (AC), 50W (DC)