Low Voltage Power & Insulated Case Circuit Breakers Section 8
Trip Units
Trip Unit Characteristics (continued)
Additional Features and Characteristics Exclusive to the Enhanced MicroVersaTrip ™ PM Trip Unit 1
Trip Unit Suffix
Function
Description
M (Metering)
P (Relaying)
PM (Metering & Relaying)
STD
STD
STD
Communications Amperes (A, kA) 2
—POWER LEADER Communications Bus Link
Selectable Phase Current ± 2.5%
STD
STD
STD
L-L or L-N Volts ± 1.5%
• • • • • •
• • • • • •
Voltage (V)
Total Energy Usage on Brkr ± 4%
Energy (kWh, MWh, GWh)
L-L or L-N Power ± 4% L-L or L-N Power ± 4% Circuit Frequency ± 1Hz
Real Power (kW/MW)
Total Power (kVA/MVA)
Frequency (Hz)
Demand & Peak Demand (kW)
—Adjustable pickup 50-90% —Adjustable delay, 1-15 seconds OFF —Adjustable pickup, 110-150% —Adjustable delay, 1-15 seconds OFF —Adjustable pickup, 10-50% —Adjustable delay, 1-15 seconds OFF —Adjustable pickup, 10-50% —Adjustable delay, 1-15 seconds OFF —Adjustable pickup, 10-990 kW —Adjustable delay, 1-15 seconds OFF —Power Reversal Direction
•
•
Under Voltage Trip
•
•
Over Voltage Trip
•
•
Voltage Unbalance
•
•
Current Unbalance
• •
• •
Power Reversal
1 MicroVersaTrip ™ PM functions require 24 Vdc control power. 2 Ampere reading also standard on MicroVersaTrip ™ Plus trip units.
Rev. 1/19 Data subject to change without notice