GE Products BuyLog Smart Catalog

Low Voltage Power & Insulated Case Circuit Breakers Section 8

Power Break ™ II Circuit Breakers Trip Unit Characteristics

Power+ Trip Unit Characteristics

Long-Time

Short-Time

Sensor Rating (Amperes) (S)

Envelope Size

Frame Max. Ampere Rating

Current Setting (C) (Pick-Up) Multiple of Rating Plug Amperes (X)

Pick-up (Multiple of Current Setting) (C)

Delay 1 (Seconds 4 Bands)

Delay (Seconds 3 Bands)

800

200, 400, 800

I 2 T in 1 .10, .21, .35

1600

800, 1000, 1600

2000

1.5, 2.0, 2.5, 3.0, 4.0, 5.0, 7.0, and 9.0

0.5, 0.6, 0.7, 0.8, 0.9, 0.95 and 1.0

2.4, 4.9, 9.8, 20

2000

2000

I 2 T out 2 .10, .21, .35

3000

2500, 3000

1000, 2000, 2500, 3000

4000

4000

4000

Power+ Trip Unit Characteristics (continued)

Ground Fault

Pick-Up (Multiple of Sensor Ampere Rating)

Adjustable Instantaneous Pick-Up without ST (Multiple of Rating Plug Amperes) (X)

Adjustable Instantaneous Pick-Up with ST (Multiple of Rating Plug Amperes) (X)

Delay 3 (Seconds 3 Bands)

Envelope Size

1.5 thru 10.0

1.5 thru 15.0

0.20 thru 0.60

I 2 T in 4 .10, .21, .35

1.5 thru 10.0

1.5 thru 15.0

0.20 thru 0.60

2000

1.5 thru 10.0

1.5 thru 15.0

0.20 thru 0.60

I 2 T out 2 .10, .21, .35

3000

1.5 thru 10.0

1.5 thru 13.0

0.20 thru 0.37

4000

1.5 thru 9.0

1.5 thru 9.0

0.20 thru 0.30

Enhanced MicroVersaTrip ™ Plus and PM Trip Unit Characteristics

Long-Time

Short-Time

Sensor Rating (Amperes) (S)

Current Setting (C) (Pick-Up) Multiple of Rating Plug Amperes (X)

Pick-up (Multiple of Current Setting) (C)

Frame Max. Ampere Rating

Delay 2 (Seconds)

Delay (Seconds)

Envelope Size

800

800

200, 400, 800

I 2 T in 1 0.40

1600

1600

800, 1000, 1600

0.5 thru 1.0 in increments of 0.05

1.5 thru 9.0 in increments of 0.5

2000

2000

2000

2.4, 4.9, 9.8, 20

2500

1000, 2000, 2500

3000

I 2 T out 2 .10, .21, .35

3000

3000

4000

4000

4000

Trip Unit Characteristics (continued)

Ground Fault

Adjustable Instantaneous Pick-Up without ST (Multiple of Rating Plug Amperes) (X)

Adjustable Instantaneous Pick-Up with ST (Multiple of Rating Plug Amperes) (X)

High Range Instantaneous (Multiple of Frame Short-Time Rating) (H)

Delay With l 2 T In Seconds

Delay 3 With l 2 T Out Seconds

Pick-Up (Multiple of Sensor Ampere Rating)

Envelope Size

1.5 thru 10.0 in 0.5 increments 1.5 thru 10.0 in 0.5 increments 1.5 thru 10.0 in 0.5 increments 1.5 thru 10.0 in 0.5 increments 1.5 thru 9.0 in 0.5 increments

1.5 thru 15.0 in 0.5 increments 1.5 thru 15.0 in 0.5 increments 1.5 thru 15.0 in 0.5 increments 1.5 thru 13.0 in 0.5 increments 1.5 thru 9.0 in 0.5 increments

0.20 thru 0.60 in increments of 0.01 0.20 thru 0.60 in increments of 0.01 0.20 thru 0.60 in increments of 0.01 0.20 thru 0.37 in increments of 0.01 0.20 thru 0.30 in increments of 0.01

800

1600

.44 at 200% of pick-up at lower limit of band

2000

1.0

.10, .21, .35

3000

4000

1 Time delay shown at 600% of current setting at lower limit of band. 2 Time delay shown at lower limit of each band. All pick-up tolerances are ± 10%. 3 Time delay shown at lower limit of each band. Ground fault pick-up not to exceed 1200 amperes. 4 Time delay shown at 200% of pick-up at lower limit of band.

S = Sensor amp rating C = Long-time current setting (pick-up) H = Short-Time Rating X = Rating plug amps

Rev. 1/19 Data subject to change without notice

go.abb/industrial

GE Products BuyLog

8-97

Made with FlippingBook - Online magazine maker