GE Products BuyLog Smart Catalog

Low Voltage Power & Insulated Case Circuit Breakers Section 8

Power Break ™ II Circuit Breakers Trip Unit Selection

5. For replacement trip units, add suffix “R”. Check Elitenet ™ for List Price and GO schedule. Example: 1600 Ampere frame, 1000 ampere sensor, Long-time (L). Short-time (S), Instantaneous (I), MicroVersaTrip ™ PM with metering only. Order B210LSIM. The replacement trip unit product number would be B210LSIMR.

How to Order 1. Determine the basic trip unit product number. 2. Determine the type of trip unit, EntelliGuard ™ TU , Power+, MicroVersaTrip ™ Plus or MicroVersaTrip ™ PM trip unit. 3. Select the trip unit suffix representing the protection function to complete trip unit product number. 4. Order rating plug separately.

Power Break ™ II Trip Unit Suffix Power+ Trip Unit Suffix Selection

Basic Trip Unit Selection

Enhanced MicroVersaTrip ™ Plus and MicroVersaTrip ™ PM Trip Units

Frame Size (Amperes)

Frame Rating (Amperes)

Trip Unit Suffix 1

EntelliGuard ™ TU Trip Unit

Sensor (Amperes)

Power+ ™ Trip Units

Trip Indicators

Long-Time (L)

Short-Time (ST)

Inst. (l)

L/ST/I 1

GF 2

Adjustable Instantaneous

GB102 GB105 GB108 GB108 GB210 GB316 GB320 GB310 GB420 GB425 GB530 GB740

200

D202

B202

LI

• • • • • •

800

800

400

D204

B204

LIT

800

D208

B208

LIT2

800

D208

B208

— —

LSI

• • •

1600

1000

D210

B210

1600-2000

LSIT1

1600

D216

B216

LSIT2

2000

2000

D220

B220

1 For high-range instantaneous or zone selective interlocking select MicroVersaTrip ™ Plus or PM trip units. 2 For ground fault-protection, select appropriate rating plug.

1000

D210

B210

2500

2000

D220

B220

2500-3000

2500

D325

B325

3000

3000

D330

B330

4000

4000

4000

D440

B440

EntelliGuard ™ TU with Selectable Phase Ammeter - Trip Indicators Standard Overcurrent Trip Selectable Phase Long-Time Long-Time with Switchable Inst

Ground Fault Ground Fault

GF/ST Zone Interlock (ZSI) 3

Suffix 1 1

Protections

Indicators

Ammeter

(L)

Fuse Settings (J)

Short-Time (ST)

(I)

(G)

Alarm (GA)

• • • •

• • • •

• • • •

• • • •

• • • •

opt. opt. opt. opt.

L3** L4** L5** L8**

LSI (S, switchable) LSIG (S, switchable) LSIGA (S, switchable)

• • •

LSIGDA (GF/S, switchable) 2

1 Add suffix to basic trip unit to product number. 2 Defeatable/Switchable Ground Fault, not UL Listed.

MicroVersaTrip ™ Plus with Selectable Phase Ammeter—Trip Indicators Standard

Trip Unit Suffix 3

Ground Fault (G) 4

GF Zone Interlock (Z1) 5

GF/ST Zone Interlock (Z2) 5

Trip Indicators

Selectable Phase Ammeter

Long-Time (L)

Short-Time (ST)

Inst. (I)

High Inst. (H)

Adjustable Instantaneous

LI

LIG

• •

• •

• •

• • • • • •

LIG Z1 LSI LSIG LSIGZ1 LSIGZ2

• • • • • • • •

• •

Fixed High Range Instantaneous 6

LSH LSHG

• • • •

• • • •

• • • •

• • • •

• •

LSHGZ1 LSHGZ2

3 Add suffix to basic trip unit product number. 4 For single-phase 3 wire or 3-phase, 4-wire applications, order appropriate neutral current sensor separately, page 8-123. Defeatable Ground Fault (not UL Listed) is available. Use code GD in place of G.

5 Requires purchase of Zone Selective Interlock module(s) Type TIM1 (120 Vac control voltage). 6 Not available on 4000A stationary breaker frame.

Rev. 1/19 Data subject to change without notice

go.abb/industrial

GE Products BuyLog

8-111

Made with FlippingBook - Online magazine maker