GE Products BuyLog Smart Catalog

HPC ™ , New Generation High-Pressure Contact Switch EntelliGuard ™ Control Unit Nomenclature Disconnect Switches and Operating Mechanisms

Section 9

EntelliGuard ™ Control Unit Nomenclature

1 Char 3

X Char 13

X Char 14

X Char 15

G F Char 1-2

0 8 Char 4 & 5

L W Char 6 & 7

X Char 8

X Char 9

X Char 10

R Char 11

X Char 12

Control Unit Form GF = HPC New Generation

Frame Rating 1 = 800A

Reserved

Sensor Rating 08 = 800A

Reserved

OC and GF Protection Packages LW = GF Only

Zone Selective Interlocking X = None

Reserved

Advanced Features and Communications X = None Selected

Reserved

Manual/Auto Trip Reset X = None

Original Factory or Replacement Control Unit R = Replacement

Character 1 & 2 EntelliGuard ™ Control Unit Form

Character 8 Zone Selective Interlocking

Character 1 & 2

Character 8

None

X Z T

HPC ™ , New Generation

GF

G user selectable

Z+IOC user selectable

Character 3 Frame Ratings

Character 3

Character 9 Advanced Features and Communications Character 9 None Selected X RELT 1 RELT+Modbus 2 Modbus-Adv Meter+WFC +RELT 6 Modbus-Adv Meter+WFC+RELT+relay 8 Modbus Only (No RELT) A Adv Metering, Modbus (No RELT) D Adv Metering, Modbus, Relays (No RELT) E

800A

1 2 3 4 5 7

1600A 2000A 2500A 3000A 4000A

Note: Use 1600A CT w/ 1200A rating plug for 1200A HPC ™ frame.

Character 4 & 5 Sensor Rating (Amperes)

Character 4 & 5

800A

08 16 20 25 30 40

Character 10 Manual/Auto Trip Reset

1600A 2000A 2500A 3000A 4000A

Character 10

None

X

Character 11 Original Factory or Replacement Control Unit Character 11 Factory F Replacement R

Character 6 & 7 OC and GF Protection Packages

Character 6 & 7

Fuse Only

LZ S1 S2 S3 S4 S5

I (Switchable)

IG (I Switchable) IGA (I Switchable)

IGDA (All Switchable) 1 GDA (All Switchable) 1

G

LW

GA

LY

1 G switchable by password only

Rev. 1/19 Data subject to change without notice

GE Products BuyLog

go.abb/industrial

9-10