Spectra ™ Series Busway Application

Cubic Inches Required per Floor and Wall

UL Fire-Stop System UL listed three-hour fire-stop barrier is now available for use with GE Busway systems. The system is listed in the UL Fire Resistance Directory under section 3L73—Through-Penetration Fire-Stop Sys- tems. In addition to the three-hour test, the system has met the criteria of ASTM E814 (UL1479). The contractor installs a mineral wool batt (4 PCF Nominal) as shown below, on-site during the busway installation process. For riser applications, the system is used in combination with a stan- dard GE spring hanger and floor flange. For horizontal applica- tions, the system is used in combination with two wall flanges (one per side).

SEALANT 100 FLOOR

SEALANT 100 WALL

Al

Cu

Al

Cu

Amperage

225-600

17

17

34

34

800

21

17

42

34

1000

22

18

44

42

1200

23

20

46

44

1350

27

22

54

46

1600

28

23

56

54

2000

33

27

66

56

2500

46

33

92

66

3000

53

44

106

92

4000

66

53

132

106

5000

66

132

GE Busway

½" Thick Minimum Sealant 100

Floor/Wall Flange

Description

Container

Product Number

Top of Floor/Curb or Wall

Sealant 100

19 cu. in.-Tube

SBFB100

You have two options for ordering the fire-stop material: 1. With initial busway purchase. Use the product numbers listed above and the fire-stop material will be shipped in a specially marked box directly to the job site with the busway. 2. Through 1-800-GE 1-STOP or an authorized GE Silicones Distributor. Recommended for fill-in (if needed) after initial purchase. This information is provided as a guideline for typical fire-stop systems. If you have an annulus (or opening) greater than 1” beyond the busway enclosure, you will need to determine the proper amount of fire-stop material based on the illustration on this page. Quantities are based on application of recommended amount of material; more may be required if over-application occurs.

Floor

Mineral Wool 3" Depth Minimum

Concrete 4 ½" Thick Minimum

Note: The Busway cover plate and sealant is required on both sides for wall installation.