GE Products BuyLog Smart Catalog

Busway

Section 13

Spectra ™ Series Busway Sandwich Bus Dimensions and Weights End Cable Tap Boxes

No. of Conductor “C” Cable No. of #2-600kcmil Stacks Material Amperage Width (in.) Height (in.) Bend Space Lugs/Ø N & GRD 1 Aluminum 225 Amps 17 26 15 1 1 Aluminum 400 Amps 17 26 15 2 1 Aluminum 600 Amps 17 26 15 2 1 Aluminum 800 Amps 17 26 15 3 1 Aluminum 1000 Amps 17 26 15 3 1 Aluminum 1200 Amps 20 29 18 4 1 Aluminum 1350 Amps 20 29 18 4 1 Aluminum 1600 Amps 20 29 18 5 1 Aluminum 2000 Amps 26 29 18 6 2 Aluminum 2500 Amps 26 29 18 8 2 Aluminum 3000 Amps 33 34 23 9 2 Aluminum 4000 Amps 33 34 23 12 1 Copper 225 Amps 17 26 15 1 1 Copper 400 Amps 17 26 15 2 1 Copper 600 Amps 17 26 15 2 1 Copper 800 Amps 17 26 15 3 1 Copper 1000 Amps 17 26 15 3 1 Copper 1200 Amps 20 29 18 4 1 Copper 1350 Amps 20 29 18 4 1 Copper 1600 Amps 20 29 18 5 1 Copper 2000 Amps 26 29 18 6 1 Copper 2500 Amps 26 29 18 8 2 Copper 3000 Amps 33 34 23 9 2 Copper 4000 Amps 33 34 23 12 2 Copper 5000 Amps 39 34 23 15 Center Cable Tap Boxes No. of Conductor “C” Cable No. of #2-600kcmil Stacks Material Amperage Width (in.) E L Bend Space Lugs/Ø N & GRD 1 Aluminum 225 Amps 24 4.38 20 15 1 1 Aluminum 400 Amps 24 4.38 20 15 2 1 Aluminum 600 Amps 24 4.38 20 15 2 1 Aluminum 800 Amps 24 4.38 20 15 3 1 Aluminum 1000 Amps 24 4.38 20 15 3 1 Aluminum 1200 Amps 30 6 28 18 4 1 Aluminum 1350 Amps 30 6 28 18 4 1 Aluminum 1600 Amps 30 6 28 18 5 1 Aluminum 2000 Amps 36 9 28 18 6 2 Aluminum 2500 Amps 36 9 32 18 8 2 Aluminum 3000 Amps 48 12.75 39 23 9 2 Aluminum 4000 Amps 48 12.75 39 23 12 1 Copper 225 Amps 24 4.38 20 15 1 1 Copper 400 Amps 24 4.38 20 15 2 1 Copper 600 Amps 24 4.38 20 15 2 1 Copper 800 Amps 24 4.38 20 15 3 1 Copper 1000 Amps 24 4.38 20 15 3 1 Copper 1200 Amps 30 6 28 18 4 1 Copper 1350 Amps 30 6 28 18 4 1 Copper 1600 Amps 30 6 28 18 5 1 Copper 2000 Amps 36 9 28 18 6 1 Copper 2500 Amps 36 9 32 18 8 2 Copper 3000 Amps 48 12.75 39 23 9 2 Copper 4000 Amps 48 12.75 39 23 12 2 Copper 5000 Amps 48 12.75 46 23 15

End Tap Box: Feeder or Plug-In

AØ BØ CØ N

"Ø SIDE"

Standard Box Down Position, Side View

Inverted Box Up Position, Side View

Center Tap Box: Feeder or Plug-in

2000 Amp (Max.) Center Branch Tap Boxes

Number of #2-600

"C" Cable Bend Space

kcmil Lugs/ N & Grd

Inverted Box Up Position, Side View

Aluminum

Copper

No. of Stacks

Width Dimension "E" Length Width Dimension "E" Length

Amperage

— 36

1

2500

9

28

18

6

2500

36

9

28

18

6

3000

43

12.75

28

43

12.75

28

18

6

2

4000

43

12.75

28

43

12.75

28

18

6

— 43

5000

12.75

28

18

6

Mechanical-type (CU-AI wires) lugs standard; Crimp-type optional. Important: Local code requirements can affect the dimensions, number of lugs furnished, etc. In these situations, refer to Company.

Standard Box Down Position, Side View

Rev. 1/19 Data subject to change without notice

go.abb/industrial

GE Products BuyLog

13-39

Made with FlippingBook - Online magazine maker