GE Products BuyLog Smart Catalog
Busway
Section 13
Spectra ™ Series Busway Sandwich Bus Power Takeoffs Dimensions
Power Takeoff Device Dimensions (Fig. 2)
Rating
Type
"H"
"W"
"D"
100A
QMR
17.75
9.38
6.75
200A
QMR
24.38
15.50
7.25
400A
QMR
18
18.50
17.56
Power Takeoffs (PTO) 1 Spectra ™ Series Flex-A-Tap joints accept bolted power takeoff devices up to 1600 amps for many applications. The compact size and flexibility resulting from the modular design allow takeoffs to be mounted at any joint, whether feeder or plug-in. See Fig. 1.
400A
QMW
18
18.50
17.56
600A
QMR
24
18.50
17.56
800A & 1200A
QMR
45.13
36.75
12.75
225A
FJ
17.75
9.75
7.75
400A
JJ
24
15.50
10.75
600A
JK
24
15.50
10.75
600-800A
KM
36
15.50
10.75
Bolt-On Tap
Amp Rating
1200A
K4V, KL4V, KM, KH, KL
45.50
15.50
10.75
With or Without Ground Fault
Fusible Switches (600A QMW Only)
600
30
15.50
10.75
400A
TB4 Tri-Break ™
Molded-Case Circuit Breakers (KM & PB Only)
1600A Max
600A
TB6 Tri-Break
44.75
15.50
10.75
Cable Boxes
1600 Max
800A
TB6 Tri-Break
49.75
15.50
10.75
150A
TE & TB1
17.75
9.75
6.75
Meter Mod III PTO Section (Fig. 3)
Dimensions (Inches)
H
D
W
Product Number/Frame
Bused Main Breakers
19
18
TMP3BR4/TJK4
5.94
19
18
TMP3BL6/TJK6
5.94
TMP3BR6/TJK6
5.94
19
18
Fig. 1 Bolt on, Flex-A-Tap Fig. 2 Flatwise PTO Section
TMP3BL8/TKM8
20
18
7.88
TMP3BR8/TKM8
20
18
7.88
20
18
TMP3BL10/TKM10
7.88
20
18
TMP3BR10/TKM10
7.88
20
18
7.88
TMP3BL12/TKM12
20
18
TMP3BR12/TKM12
7.88
Bused Main Switches
TMP3FL4/TFUSE400
19
18
5.94
TMP3FR4/TFUSE400
19
18
5.94
TMP3FL6/TFUSE600
19
18
5.94
TMP3FR6/TFUSE600
19
18
5.94
Fig. 3 Meter Mod III PTO Section available with no device. Check local codes before ordering
Bar Per ø
Amps
Bar Width (inches)
"A" (inches)
1.625 2.225 2.875 3.375 4.250 4.500 5.750 6.500 8.250 4.250 4.500 5.750 6.500 8.250
225-1200 Al 225-1600 Cu
16.50
1
1350-2000 Al 2000-2500 Cu
20.00
2500 Al 3000 Cu
24.75
Fig. 4 Meter-mod Metering (in line device) Available for G&K Frame Spectra ™ C/B only
2
3000-4000 Al 4000-5000 Cu
32.00
Flex-A-Tap Device (Fig. 1)
Decimal
Fraction
Device
"H"
"W"
"D"
.12
1/8
Cable Tap Box
54"
24"
15 1/2"
.38
3/8
KM
66"
19 9/32"
15 1/2"
.63
5/8
QMW 600A
66"
19 9/32"
15 1/2"
.88
7/8
Power Break II
63"
24 9/32"
18"
1 TMZR mounting Z-rail must be added for the attached Meter Mod.
Rev. 1/19 Data subject to change without notice
go.abb/industrial
GE Products BuyLog
13-43
Made with FlippingBook - Online magazine maker