GE Products BuyLog Smart Catalog

Uninterruptible Power Supplies Energy Connections SG Series 225-300 kVA Three-Phase External Maintenance Bypass Cabinets

Section 20

Series SG UPS - 3 Breaker Matching, Free Standing Maintenance Bypass Cabinet (MBC)

SG UPS kVA 225kVA 225kVA 300kVA 300kVA

UIB CB (Trip Rating)

MIB & MBB CB (Trip Rating)

Height (in)

Weight (lbs)

kAIC Rating @ 480VAC

Width (in)

Depth (in)

Product Number

450AT (80%) 450AT (80%) 600AT (80%) 600AT (80%)

350AT (80%) 350AT (80%) 500AT (80%) 500AT (80%)

35kAIC 65kAIC 35kAIC 65kAIC

30 30 30 30

32.8 32.8 32.8 32.8

71 71 71 71

400 400 400 400

MBC224-354500-L300 MBC224-354500-L600 MBC304-506000-L300 MBC304-506000-L600

Notes on SG Matching MBC: 1. Cabinets are matching height, depth, and black color same as UPS Module 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. Neutral not used in 3w UPS applications. 3. Base MBC includes 3-breaker with mechanical Kirk Key configuration.

For 3-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #15 to "K", example: MBC224-354000-K600 For 2-breaker MBC with mechanical Kirk Key change, the Base MBC, digit #10 & #11 to "00", example: MBC224-350000-L600 For 2-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #10 & #11 to "00" and digit # 15 to "K", example: MBC224-350000-K600

4. Cabinet conduit access via top, bottom, and sides via knockouts. 5. Warranty is 1 year. Leadtime is 4-6 (typical) weeks via sourced supplier.

Series SG UPS - 3 Breaker Non-Matching, Wall Mount Maintenance Bypass Panel (MBP) - Style A

SG UPS kVA 225kVA 225kVA 300kVA 300kVA

UIB CB (Trip Rating)

MIB & MBB CB (Trip Rating)

kAIC Rating @ 480VAC

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Product Number

450AT (80%) 450AT (80%) 600AT (80%) 600AT (80%)

350AT (80%) 350AT (80%) 500AT (80%) 500AT (80%)

35kAIC 35kAIC 35kAIC 35kAIC

40 40 40 40

14 14 14 14

91 91 91 91

557 557 557 557

GS20350-10450-A1S GS20350-10450-A2S GS20500-10600-A1S GS20500-10600-A2S

Notes on SG Non-Matching MBP Wallmount Panelboard: 1. Cabinets are ANSI grey (switchgear) color 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. Neutral not used in 3w UPS applications. 3. Circuit Breaker interlock system is a Kirk Key mechanical, with detailed operational instructions included. Electrick interlock (w/SKRU) is an option. 4. Cabinet conduit access via top and bottom via knockouts. 5. Warranty is 1 year. Leadtime is 4-8 weeks (typical) via GE factory.

Series SG UPS - 3 Breaker, Wall Mounted Maintenance Bypass Panel (MBP) - Style B

SG UPS kVA 225kVA 225kVA 300kVA 300kVA

UIB CB (Trip Rating)

MIB & MBB CB (Trip Rating)

kAIC Rating @ 480VAC

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Product Number

450AT (80%) 450AT (80%) 600AT (80%) 600AT (80%)

350AT (80%) 350AT (80%) 500AT (80%) 500AT (80%)

35kAIC 65kAIC 35kAIC 65kAIC

36 36 36 36

14 14 14 14

48 48 48 48

140 140 140 140

MBP224-354500-L300 MBP224-354500-L600 MBP304-506000-L300 MBP304-506000-L600

Notes on SG Wallmount MBPs: 1. Cabinets are black in color. 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. Neutral not used in 3w UPS applications. 3. Base MBP includes 3-breaker with mechanical Kirk Key configuration.

For 3-breaker MBP with electric interlock (with SKRU) change, the Base MBP, digit #15 to "K", example: MBC224-354000-K600 For 2-breaker MBP with mechanical Kirk Key change, the Base MBP, digit #10 & #11 to "00", example: MBC224-350000-L600 For 2-breaker MBP with electric interlock (with SKRU) change, the Base MBP, digit #10 & #11 to "00" and digit # 15 to "K", example: MBC224-350000-K600 4. Cabinet conduit access top and bottom via knockouts. 5. Warranty is 1 year. Leadtime is 3-5 weeks (typical) via sourced supplier.

Series SG UPS - 4x2 Combo, 3 Breaker Maintenance Bypass Cabinet (MBC) w/Output Isolation Transformer

SG UPS KVA

UIB CB (Trip Rating)

MIB & MBB CB (Trip Rating)

kAIC Rating @ 480VAC

Width (in)

Depth (in)

Height (in)

Weight (lbs)

Product Number

225 225

450AT (80%) 450AT (80%)

350AT (80%) 350AT (80%)

35kAIC 65kAIC

36 36

33 33

71 71

1650 1650

MBC224-354500-L322 MBC224-354500-L622

Notes on SG 4x2 combo MBC: 1. Cabinets are matching depth, height, black color of UPS Module 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. K13 DOE2016 Compliant copper transformer, 480V-208/120V 3. Base 4x2 Combo MBC includes 3-breaker with mechanical Kirk Key configuration.

For 4x2 Combo 3-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #15 to "K", example: MBC224-354000-K622 For 4x2 Combo 2-breaker MBC with mechanical Kirk Key change, the Base MBC, digit #10 & #11 to "00", example: MBC224-350000-L622 For 4x2 Combo 2-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #10 & #11 to "00" and digit # 15 to "K", example: MBC224-350000-K622 4. Cabinet conduit access top and bottom via knockouts. 5. Warranty is 1 year. Leadtime is 6-8 weeks (typical) via sourced supplier.

Rev. 1/19 Data subject to change without notice

GE Products BuyLog

go.abb/industrial

20-48

Made with FlippingBook - Online magazine maker