Killark Full Catalog
CONTROLS XAL/XAS SERIES
FIRE ALARM STATIONS
Class I, Div. 1 & 2, Groups C, D Class l, Zones 1 & 2, Groups llB, llA Class II, Div. 1 & 2, Groups E, F, G Class Ill
XAL Series:
- F i l e E 5 0 4 9 8
C e r t i f i e d - F i l e L R 3 10 8 5
XAS Series:
- F i l e E50498
Ce r t i f i ed - F i l e LR31085
XAL Pull Ring
XAS Break Glass
FEATURES-SPECIFICATIONS Features • Conduit openings are 3/4” NPT feed through • Red, textured powder epoxy paint finish is standard on box and cover and provides high visibility for alarm station • XAL-458 has (2) normally open and (2) normally closed contacts. • Bilingual nameplates included per CSA requirement • Internal ground screw is standard
Materials • Enclosure is made of copper free aluminum alloy • XAS Lens – Glass • External Hardware – Stainless Steel
Electrical Rating • Push button stations, selector switches
heavy duty 600 VAC max. • Pilot lights 250 VAC max.
CONTACT BLOCK RATINGS – A600 CURRENT 120 VAC 240 VAC 480 VAC 600 VAC INRUSH 60 30 15 12 BREAKING 6 3 1.5 1.2 CARRYING 10 10 10 10 DC RATINGS (MAX. AMPS) – P600 CURRENT 125 VAC 250 VAC INRUSH 55 .27 BREAKING 55 .27 CARRYING 2.55 2.55
• XAL: The alarm station is activated by lifting the front cover and pulling down ring. This quick, easy to use two-step process prevents unintentional operation. • XAS: Breaking glass with hammer provided activates alarm. Reset by replacing glass.