Steam Generator & Fluid Heater Installation Manual

1.1.15 System Steam Traps The steam traps in the system must be rated for the system pressure, and sized for the dif- ference between the steam system and the receiver. This usually requires the traps be one size larger than on an open system. The steam traps in the system must be properly maintained for the system to function normally. If there are traps “blowing by,” the SCR will be pressurized above the BPR set point and steam will be needlessly vented to atmosphere. 1.1.16 A General Statement Because of the uniqueness of an SCR system, the requirements put forth here must be closely followed to ensure trouble free operation. If properly installed and maintained the Clayton Semi-closed Receiver System will operate with a high degree of reliability and economic bene- fits.