BuyLog Flippingbook JUN 2024
METERING, BUYLOG SECTION 2
2-51
— ReliaMod™ Series ratings Two-tier series ratings guide for modular metering
UL two-tier series connected rating UL permits assigning a short-circuit rating (kAIC) to a combination of overcurrent protection devices connected in series that is higher than the lowest rated overcurrent protection device in the combination. This allows you to use lower kAIC downstream breakers, thus reducing the cost of your project. Series rating with UL standards in multi-family applications using the ABB empower configurator in conjunction with ABB series rating publication DET-008 can greatly reduce the total cost of your bill of material. A two-tier series rating is common in a multi-family application with ABB ReliaMod™ modular metering. It consists of two levels of overcurrent protection devices as outlined in the illustration. • Tier 1: The meter center or switchboard main breaker • Tier 2: The meter stack tenant breakers
A two-tier series rating system occurs when there is a UL tested and approved combination of two levels of overcurrent protection. In this system the short circuit rating of the upstream protector is fully rated at its location, but the downstream overcurrent protector is not fully rated and has a lower interruption rating (kAIC) than the available fault current at its location. This is allowable by UL. The below tables are a quick reference guide of some common UL recognized ABB two-tier series rating combinations between main breakers in meter centers (or switchboards) to downstream tenant breakers in meter stacks. This is a guide only, not all inclusive, and does NOT serve as official documentation. Please refer to the latest version of ABB series rating publication DET-008 for the latest official UL recognized series ratings and documentation.
Meter center or switchboard main breaker (Tier 1) Meter stack tenant breaker (Tier 2)
Two-tier series combinations for 125A socket applications Meter stack application Upstream device (Tier 1)
Downstream device (Tier 2)
Series rated interrupting rating
Socket amperage
Main breaker frame
Tenant breaker frame
Amperage
Poles
Amperage 70A-125A 60A-125A 60A-125A 70A-125A 60A-125A 70A-125A 60A-125A 70A-125A 70A-125A
Poles
Symmetrical amps
Phase
Vac 240
125A
T8V 1400A-2000A 2 and 3
THQL
2 2 2 2 2 2 2 2 2
42,000 65,000 100,000 65,000 100,000 65,000 100,000 65,000 100,000
1 1 1 1 1 1 1 1 1
TEY or TEYF
TEYL THQL
XT7S 1000A-1200A 2 and 3
XT7H XT6N XT6S
TEY or TEYF
800A 2 and 3
THQL
TEY or TEYF
XT5N 400A-600A 2 and 3
THQL THQL
XT5S
Two-tier series combinations for 225A socket applications Meter stack application Upstream device (Tier 1)
Downstream device (Tier 2)
Series rated interrupting rating
Socket amperage
Main breaker frame
Tenant breaker frame
Amperage
Poles
Amperage 40A-225A
Poles
Symmetrical amps
Phase
Vac 240
225A
T8V 1400A-2000A 2 and 3 Formula A1N or A2N
2 65,000 and 100,000
1 1 1 1 1 1 1 1 1 1 1
E2.2SF (Emax 2) E2.2VF (Emax 2)
2 2 2 2 2 2 2 2 2 2
65,000 100,000 65,000 100,000 65,000 100,000 65,000 100,000 65,000 100,000
SS (PBII) SH (PBII)
XT7S 1000A-1200A 2 and 3 Formula A1N or A2N
40A-225A
XT7H XT6N XT6S
800A 2 and 3 Formula A1N or A2N
40A-225A
XT5N 400A-600A 2 and 3 Formula A1N or A2N
40A-225A
XT5S
Made with FlippingBook Digital Publishing Software