BuyLog Flippingbook MAR 2024

6-59

MOLDED CASE CIRCUIT BREAKERS, BUYLOG SECTION 6

— Industrial Circuit Breakers 15-100A Thermal Magnetic Trip Type TEY/TEYF Noninterchangeable Trip Bolt-on 480Y/277V Class

TEY and TEYF breakers are one-inch wide per pole, compact, bolt-on circuit breakers for use on grounded 480Y/277 Vac systems. Short circuit ratings at that voltage for TEY and TEYF are 14 and 18kA, respectively. TEYF also offers higher selectivity ratings with upstream devices (See DET-537 for details). The bolt-on mounting base (TEY3B) shown on page 6-177 makes TEY and TEYF suitable for various lug-lug applications.

TEY/TEYF (UL/cUL File E-11592) Ampere Rating Wire Range 1

Product Number

Product Number

Type TEYF 3, 4 18kA @ 277 Vac

Type TEY 3, 4 14kA @ 277 Vac

Single Pole - Includes Integral Cu/Al Load Lugs

# 14- # 10 # 14- # 10 # 10 -# 4 # 10 -# 4 # 10- # 4 # 10- # 4 # 10- # 4 # 10- # 4 # 10- # 4

TEYF115 2 TEYF120 2 TEYF125 TEYF130 TEYF135 TEYF140 TEYF145 TEYF150 TEYF160

15 20 25 30 35 40 45 50 60 70 80 90 15 20 25 30 35 40 45 50 60 70 80 90 15 20 25 30 35 40 45 50 60 70 80 90

TEY115 2 TEY120 2 TEY125 TEY130 TEY135 TEY140 TEY145 TEY150 TEY160 TEY170 TEY180 TEY190 TEY1100 TEY215 TEY220 TEY225 TEY230 TEY235 TEY240 TEY245 TEY250 TEY260 TEY270 TEY280 TEY290 TEY2100 TEY315 TEY320 TEY325 TEY330 TEY335 TEY340 TEY345 TEY350 TEY360 TEY370 TEY380 TEY390 TEY3100 – –

1- 2- and 3-pole TEY/TEYF breakers

# 4-1/0 # 4-1/0 # 4-1/0 # 4-1/0

– – – –

100

Type TEYF 3, 4 18kA @ 480 / 277 Vac

Type TEY 3, 4 14kA @ 480 / 277 Vac

Two-Pole - Includes Integral Cu/Al Load Lugs

# 14- # 10 # 14- # 10 # 10 -# 4 # 10 -# 4 # 10- # 4 # 10- # 4 # 10- # 4 # 10- # 4 # 10- # 4

TEYF215 TEYF220 TEYF225 TEYF230 TEYF235 TEYF240 TEYF245 TEYF250 TEYF260 TEYF270 TEYF280 TEYF290 TEYF2100 TEYF2110B TEYF2125B TEYF315 TEYF320 TEYF325 TEYF330 TEYF335 TEYF340 TEYF345 TEYF350 TEYF360 TEYF370 TEYF380 TEYF390 TEYF3100 TEYF3110B TEYF3125B

# 4-1/0 # 4-1/0 # 4-1/0 # 4-1/0

100 110 125

# 3-3/0 Cu, # 1-3/0 Al # 3-3/0 Cu, # 1-3/0 Al

Type TEYF 3, 4 18kA @ 480 / 277 Vac

Type TEY 3, 4 14kA @ 480 / 277 Vac

Three-Pole - Includes Integral Cu/Al Load Lugs

# 14- # 10 # 14- # 10 # 10 -# 4 # 10 -# 4 # 10- # 4 # 10- # 4 # 10- # 4 # 10- # 4 # 10- # 4

# 4-1/0 # 4-1/0 # 4-1/0 # 4-1/0

100 110 125

# 3-3/0 Cu, # 1-3/0 Al # 3-3/0 Cu, # 1-3/0 Al

– –

1 Solid or stranded for 14-10 AWG. 2 Single-pole, 15 and 20 ampere breakers are also UL listed as switching duty breakers, suitable for switching 120, 240, or 277 Vac.

3 UL listed HACR (Heating, Air Conditioning, Refrigeration). 4 UL listed for HID (high intensity discharge), all 50A or less.

Made with FlippingBook Ebook Creator