13-9

BUSWAY, BUYLOG SECTION 13

— ReliaGear ™ series busway Application

UL fire-stop system UL listed three-hour fire-stop barrier is now available for use with ABB Busway systems. The system is listed in the UL Fire Resistance Directory under section 3L73—Through Penetration Fire-Stop Systems. In addition to the three-hour test, the system has met the criteria of ASTM E814 (UL1479). The contractor installs a mineral wool batt (4 PCF Nominal) as shown below, on-site during the busway installation process. For riser applications, the system is used in combination with a standard ABB spring hanger and floor flange. For horizontal applications, the system is used in combination with two wall flanges (one per side).

Cubic inches required per floor and wall

SEALANT 100 FLOOR SEALANT 100 WALL Al Cu Al Cu

Amperage

225-600

17 21 22 23 27 28 33 46 53 66

17 17 18 20 22 23 27 33 44 53 66

34 42 44 46 54 56 66 92

34 34 42 44 46 54 56 66 92

800

1000 1200 1350 1600 2000 2500 3000 4000 5000

106 132

106 132

ABB Busway

½" Thick Minimum Sealant 100

Description Sealant 100

Container

Product Number

Floor/Wall Flange

19 cu. in.-Tube

SBFB100

Top of Floor/Curb or Wall

You have two options for ordering the fire-stop material:

1. With initial busway purchase. Use the product numbers listed above and the fire-stop material will be shipped in a specially marked box directly to the job site with the busway. 2. Through empower or an authorized ABB Silicones Distributor. Recommended for fill-in (if needed) after initial purchase. This information is provided as a guideline for typical fire stop systems. If you have an annulus (or opening) greater than 1” beyond the busway enclosure, you will need to determine the proper amount of fire-stop material based on the illustration on this page. Quantities are based on application of recommended amount of material; more may be required if over-application occurs.

Floor

Mineral Wool 3" Depth Minimum

Concrete 4 ½" Thick Minimum

Note: The busway cover plate and sealant is required on both sides for wall installation.