BuyLog Flippingbook MAR 2024
METERING, BUYLOG SECTION 2
2-21
— ReliaMod™ Main pull box modules
Main pull box module: 1-phase 3 wire 120/240Vac (horizontal cross bus not included) Main ampere rating kAIC Wire entry Incoming line lugs per phase & neutral (AWG/kcmil Cu/Al) Outgoing load lugs per phase & neutral (AWG/kcmil Cu/Al)
Enclosure
Ordering code
(1) 250-750 kcmil or (2) 3/0-250 kcmil
N3R Outdoor
400
100
Bottom Lug landing pad accepts up to 1 wire landing per phase & neutral. Lugs not included, to be provided by others.
RMM1P4R
(2) 250-750 kcmil or (4) 3/0-250 kcmil
RMM1P8R
800
Lug landing pad accepts up to 2 wire landings per phase & neutral. Lugs not included, to be provided by others. Lug landing pad accepts up to 3 wire landings per phase & neutral. Lugs not included, to be provided by others.
(4) 250-750 kcmil or (8) 3/0-250 kcmil
RMM1P12R
1200
Main pull box module: 3-phase 4 wire 208Y/120Vac or 120/240Vac delta hi-leg (horizontal cross bus not included) Main ampere rating kAIC Wire entry Incoming line lugs per phase & neutral (AWG/kcmil Cu/Al) Outgoing load lugs per phase & neutral (AWG/kcmil Cu/Al) Enclosure
— 400A Pull Box Module: RMM3P4R
Ordering code
(1) 250-750 kcmil or (2) 3/0-250 kcmil
N3R Outdoor
400
100
Bottom Lug landing pad accepts up to 1 wire landing per phase & neutral. Lugs not included, to be provided by others.
RMM3P4R
(2) 250-750 kcmil or (4) 3/0-250 kcmil
RMM3P8R
800
Lug landing pad accepts up to 2 wire landings per phase & neutral. Lugs not included, to be provided by others. Lug landing pad accepts up to 3 wire landings per phase & neutral. Lugs not included, to be provided by others.
(4) 250-750 kcmil or (8) 3/0-250 kcmil
RMM3P12R
1200
Note: Pull boxes do not come with horizontal bussing to directly connect to a main section or meter stacks. It is for lug in, lug out applications. It comes with a line side lug landing pad (lugs not included) and load side mechanical lugs. Pull boxes can be useful for certain utilities that prefer to land their own cables in a separate enclosure and not directly on the line side of a main breaker. Note: 400A and 800A pull box models conform to EUSERC drawings 343 and 347. The 1200A pull box models do not currently meet EUSERC requirements. Note: Limited to the lowest marked short circuit rating of the main and meter modules used Note: Please click on any specific ReliaMod™ ordering code with a hyperlink to be taken to the respective outline drawing/spec sheet for the product to view additional technical details.
— 800A Pull Box Module: RMM3P8R
Main pull box module dimensions
Main pull box module: 1-phase 3 wire 120/240Vac Main ampere rating kAIC Wire entry
W (in) 16.80 24.86 32.98
H (in) 43.17 50.46 54.59
D (in)
Ordering code
400 800
100
Bottom
7.70
RMM1P4R RMM1P8R RMM1P12R
11.32 11.32
1200
Main pull box module: 3-phase 4 wire 208Y/120Vac or 120/240V delta hi-leg (horizontal cross bus not included) Main ampere rating kAIC Wire entry W (in) H (in) D (in)
Ordering code
400 800
100
Bottom
16.80 24.86 32.98
43.17 50.46 54.59
7.70
RMM3P4R RMM3P8R
11.32 11.32
1200 RMM3P12R Note: For additional dimensions and technical data please click on the specific ReliaMod™ ordering code hyperlink in this catalog to view its respective outline drawings/spec sheet. These can also be found in ABB empower and the ABB Library.
— 1200A Pull Box Module: RMM3P12R