BuyLog Flippingbook OCT 2024 v2
METERING, BUYLOG SECTION 2
2-22
— ReliaMod™ Meter stack families and their tenant breakers
ReliaMod™ meter stacks are designed to accept certain frames of tenant breakers based on the tenant breaker kAIC being used. For example: • A ringless 125A socket 6-gang meter stack that is series rated at 65 kAIC to a 1200A XT7 MCB will allow the use of 10 kAIC THQL tenant breakers, which would be a meter stack order code number of RMS28612 L RLR • That same ringless 125A socket 6-gang meter stack fully rated at 65 kAIC would utilize TEY tenant breakers, which would be a slightly different meter stack order code number RMS28612 H RLR
This feature allows ABB meter stacks to be much more flexible in design based on the specific kAIC of the application. It is always important to understand your application up front with the specific kAIC needed and what combinations of breakers can be series rated per ABB publication DET-008 in order to select the appropriate meter stacks and tenant breakers for them. The modular metering configurator in ABB empower can help assist in the correct product selection. Please see the ReliaMod™ meter stack family summary below along with the specific tenant breakers they can accept.
400A commercial lever bypass socket meter stack family
225A commercial lever bypass socket meter stack family
225A residential socket meter stack family
125A residential socket meter stack family
XT5 factory installed
XT3/XT4 style
XT3/XT4 style
Formula style
THQL style
TEY style
Tmax XT5 (TMA) 400A 65 kAIC tenant breaker(s) factory installed
Only accepts ReliaMod™ Tmax XT3/XT4 (TMF) tenant breakers 42-100 kAIC
Only accepts ReliaMod™ Tmax XT3/XT4 (TMF) tenant breakers 42-100 kAIC
Only accepts ReliaMod™
Only accepts THQL tenant breakers 10-22 kAIC¹
Only accepts ReliaMod™ TEY-MM tenant breakers 42-100 kAIC
Formula A1/A2 tenant breakers 10-22 kAIC²
THQL breaker frame
TEY breaker frame
Formula breaker frame
Tmax XT3/XT4 breaker frame
Tmax XT3/XT4 breaker frame
Tmax XT5 breaker frame
¹ Though the tennant breaker provision in these stacks accommodates a 10 or 22 kAIC fully rated THQL/THHQL/THHQL-RM breaker, you can series rate these breakers within these stacks to 65 or 100 kAIC depending on the breaker combinations you are using. Please refer to the series rating section of the BuyLog or ABB publication DET-008 for more info on series rating tenant breakers for ReliaMod™. ² Though the tennant breaker provision in these stacks accommodates a 10 or 22 kAIC fully rated Formula A1 or A2 breaker, you can series rate these breakers within these stacks to 65 or 100 kAIC depending on the breaker combinations you are using. Please refer to the series rating section of the BuyLog or ABB publication DET-008 for more info on series rating tenant breakers for ReliaMod™.