GE Products BuyLog Smart Catalog
Molded Case Circuit Breakers Record Plus ™ FE 250
Section 6
Reference Publications Available for download from www.geindustrial.com/publibrary FE Breaker
1 2 3 4 5
Breaker Frame Rating Product Description Standards & Markings Interrupting Ratings Lug Data & Torque Info Product Number Push to Trip
Installation Instructions DEH-41640 Outline Drawing 10101247PV1 FE Breaker Accessories Bell Alarm & Aux Switch DEH-40324 Shunt Trip & UVR DEH-40259 Padlock Device DEH-41059 Lug Kits DEH-41054 Auxiliary Contacts DEH-40261 Panelboards Spectra ™ Power Panel - Plug-in Kits DEH-40402 Spectra ™ Power Panel - Bolt-on Kits DEH-40425 Series Ratings DET-008 External Operators STDA Style DEH-41014 TDM Style DEH-41025 Trip Curves Record Plus FE with PremEon S Trip - LSI Protections DES-115 Record Plus FE with PremEon S Trip - GF Protection DES-116 Record Plus FE with PremEon S Trip - Mag only Motor Circuit Protector DES-117 Peak Current Curves DES-205 Peak l 2 t Curve DES-206
1
2
3
4
6 7
5
6
7
Main Standards —UL/cUL 489 —HACR (heating, air conditioning, and refrigeration) —Naval
Interrupting Ratings
UL Listed Interrupting Ratings - rms Symmetrical Amperes (in Thousands) AC Voltage
Type Ampere Rating Max Voltage No. Poles 240 480 FEN 25-250A 480VAC 2 150 65 3 150 65 FEH 25-250A 480VAC 2 200 100 3 200 100
Cross Reference SMR1 Equipped FE MCCB FE(N/H)(2/3)4AA0025R FE(N/H)(2/3)4AA0060R FE(N/H)(2/3)4AA0125R FE(N/H)(2/3)4AA0150R FE(N/H)(2/3)4AA0250R
Rating Plug Amps
PremEon Equipped MCCB FE(N/H)(2/3)4DB025KF FE(N/H)(2/3)4DB060KF FE(N/H)(2/3)4DB125KF FE(N/H)(2/3)4DB150KF FE(N/H)(2/3)4DB250KF
20, 25
25, 30, 40, 50, 60
50, 60, 70, 80, 90, 100 ,110 ,125 70, 80, 90, 100, 110, 125, 150 100, 110, 125, 150, 175, 200, 225, 250
Product Number Structure
F E N 3 4 D B 250 K F
Interruption Rating (@480VAC) N = 65kA H = 100kA
Connection Configuration F = Standard, No Lugs
Frame Size E = 250A
Trip Unit Amps 025 = 25A 060 = 60A
Frame Amps K = 250A
Trip Unit Protection B = LI G =LIG w/ Ground Fault
Family F = Record Plus
Voltage 4 = 480VAC
Trip Unit Type D = PremEon S 1
Poles 2 = 2-Pole in 3-Pole Frame 3 = 3 Pole
125 = 125A 150 = 150A 250 = 250A
1 Requires tamper-resistant Torx T15 tool for adjustment.
Rev. 1/19 Data subject to change without notice