GE Products BuyLog Smart Catalog

Molded Case Circuit Breakers Record Plus ™ FE 250

Section 6

Reference Publications Available for download from www.geindustrial.com/publibrary FE Breaker

1 2 3 4 5

Breaker Frame Rating Product Description Standards & Markings Interrupting Ratings Lug Data & Torque Info Product Number Push to Trip

Installation Instructions DEH-41640 Outline Drawing 10101247PV1 FE Breaker Accessories Bell Alarm & Aux Switch DEH-40324 Shunt Trip & UVR DEH-40259 Padlock Device DEH-41059 Lug Kits DEH-41054 Auxiliary Contacts DEH-40261 Panelboards Spectra ™ Power Panel - Plug-in Kits DEH-40402 Spectra ™ Power Panel - Bolt-on Kits DEH-40425 Series Ratings DET-008 External Operators STDA Style DEH-41014 TDM Style DEH-41025 Trip Curves Record Plus FE with PremEon S Trip - LSI Protections DES-115 Record Plus FE with PremEon S Trip - GF Protection DES-116 Record Plus FE with PremEon S Trip - Mag only Motor Circuit Protector DES-117 Peak Current Curves DES-205 Peak l 2 t Curve DES-206

1

2

3

4

6 7

5

6

7

Main Standards —UL/cUL 489 —HACR (heating, air conditioning, and refrigeration) —Naval

Interrupting Ratings

UL Listed Interrupting Ratings - rms Symmetrical Amperes (in Thousands) AC Voltage

Type Ampere Rating Max Voltage No. Poles 240 480 FEN 25-250A 480VAC 2 150 65 3 150 65 FEH 25-250A 480VAC 2 200 100 3 200 100

Cross Reference SMR1 Equipped FE MCCB FE(N/H)(2/3)4AA0025R FE(N/H)(2/3)4AA0060R FE(N/H)(2/3)4AA0125R FE(N/H)(2/3)4AA0150R FE(N/H)(2/3)4AA0250R

Rating Plug Amps

PremEon Equipped MCCB FE(N/H)(2/3)4DB025KF FE(N/H)(2/3)4DB060KF FE(N/H)(2/3)4DB125KF FE(N/H)(2/3)4DB150KF FE(N/H)(2/3)4DB250KF

20, 25

25, 30, 40, 50, 60

50, 60, 70, 80, 90, 100 ,110 ,125 70, 80, 90, 100, 110, 125, 150 100, 110, 125, 150, 175, 200, 225, 250

Product Number Structure

F E N 3 4 D B 250 K F

Interruption Rating (@480VAC) N = 65kA H = 100kA

Connection Configuration F = Standard, No Lugs

Frame Size E = 250A

Trip Unit Amps 025 = 25A 060 = 60A

Frame Amps K = 250A

Trip Unit Protection B = LI G =LIG w/ Ground Fault

Family F = Record Plus

Voltage 4 = 480VAC

Trip Unit Type D = PremEon S 1

Poles 2 = 2-Pole in 3-Pole Frame 3 = 3 Pole

125 = 125A 150 = 150A 250 = 250A

1 Requires tamper-resistant Torx T15 tool for adjustment.

Rev. 1/19 Data subject to change without notice

go.abb/industrial

GE Products BuyLog

6-79

Made with FlippingBook - Online magazine maker