GE Products BuyLog Smart Catalog

Low Voltage Power & Insulated Case Circuit Breakers Section 8

WavePro Low Voltage Power Circuit Breakers Selection (continued)

Step 2 (Cont.)

WavePro Catalog Number - Code 6 Function Long Short Non-Switchable Ground Product No. Code Time Time Instantaneous Instantaneous Fault 1 Digit LSI • • • P LSIG • • • • Q LSIGA • • • • 1 LSIGDA 2 • • • • 2 LSI 2 • • • • U LSIG 2 • • • • 7 LSIGA 2 • • • • 8 LSIGDA 3 • • • • 9 2 Switchboard Applications

MicroVersaTrip ™ Trip Unit All MicroVersaTrip ™ trip units include integral targets and ammeter display. MicroVersaTrip ™ M adds full metering and communica- tions; MicroVersaTrip ™ PM adds relaying, metering and communications.

MicroVersaTrip ™ Plus

MicroVersaTrip ™ PM

Functions

Defeatable Ground Fault 1,3

Switchable ST or Inst & GF 1,3

ZSI-GF & ST 4

Ground Fault 1

Function Code

Long Time

Short Time

Instanta- neous

Product No. Digits

Product No. Digits

Product No. Digits

ZSI-GF 4

LI

AJ

BJ

CJ

AK

BK

CK

LIG

LIGZ1 LIGD 3

AL

BL

CL

AM

BM

CM

LIGDZ1 3

AN

BN

CN

LS

AA

BA

CA

AB

BB

CB

LSG

LSGZ1

AC

BC

CC

LSGZ2 LSGD 3

AD

BD

CD

AE

BE

CE

LSGDZ1 3 LSGDZ2 3

AF

BF

CF

AG

BG

CG

LSI

AP

BP

CP

LSIG

AQ

BQ

CQ

LSIGX 3

AR

BR

CR

LSIGZ1

AS

BS

CS

AT

BT

CT

LSIGZ2 LSIGD 3

AV

BV

CV

LSIGDZ1 3 LSIGDZ2 3

AW

BW

CW

AY

BY

CY

1 Ground fault is 3-wire/4-wire. If 4-wire ground fault is required, then one of the A-Disconnect options in Step 10 must be selected and the sensor for the 4th wire (neutral) must be ordered separately. See Table B-5 on page 8-44. 3 Function combination is not UL Listed.

4 Requires zone selective interlock module, Type TIM1 (120Vac control voltage).

Rev. 1/19 Data subject to change without notice

go.abb/industrial

GE Products BuyLog

8-35