Low Voltage Power & Insulated Case Circuit Breakers Section 8
Power Break ™ II Construction Options
The interruption ratings and voltages shown in the table are maximum ratings. A circuit breaker of the type given in the left- hand column may be applied at the given circuit voltage in any electrical distribution system where the available fault current at the load terminals of the breaker does not exceed the value in the table. That circuit breaker type may also be applied at intermediate values of circuit voltage provided the available fault current at the load terminals of the breaker does not exceed the value in the table for the higher value of voltage.
Insulated Case Circuit Breakers
Trip Types
Circuit Breaker
Envelope Size EntelliGuard ™ Molded Max IC @ Max Voltage Max Frame (Amperes) TU Power+ Plus/PM Case Switch 480V (kA) Rating (ac) (Amperes) MicroVersaTrip ™
Power Break ™ II
800 X X X 65 600 800 1600 X X X 65 600 1600 Standard 2000 X X X 65 600 2000 3000 X X X 100 600 3000 4000 X X X 100 600 4000 800 X X X 100 600 800 1600 X X X 100 600 1600 Hi-Break 2000 X X X 100 600 2000
3000 X X X 150 600 3000 4000 X X X 150 600 4000 800 X 30 1 600 800 1600 X 40 1 600 1600
Molded 2000 X 40 1 Case Switch 2500 X 42 1
600 2000 600 2500 600 3000 600 4000
3000 X 42 1 4000 X 42 1
1 Molded case switch ratings are short time @ 600Vac, not interrupting current. See page 8-108 for withstand ratings.
Rev. 1/19 Data subject to change without notice