Disconnect Switches and Operating Mechanisms

Section 9

HPC ™ High-Pressure Contact Switch With Integral Ground Fault Devices 800-4000 Amperes - 600 Vac Max. UL File. No. E-51827

HPC ™ Switches with Integral Ground Fault Protection for Solidly Grounded Systems Integral Ground Fault with 3-Phase Sensor, Adjustable Pick-up, Adjustable Time-Delay, Test Function, and Mechanical Ground Fault Indicator Source Ampere Net Weight Product Configuration Rating Lbs. (Approx.) Number Top Feed 800A 105 THPR3608G3T Top Feed 1200A 105 THPR3612G3T Top Feed 1600A 105 THPR3616G3T Top Feed 2000A 195 THPC3620G3T Top Feed 2500A 210 THPC3625G3T Top Feed 3000A 210 THPC3630G3T Top Feed 4000A 540 THPC3640G3T Bottom Feed 800A 105 THPR3608BG3T Bottom Feed 1200A 105 THPR3612BG3T Bottom Feed 1600A 105 THPR3616BG3T Bottom Feed 2000A 195 THPC3620BG3T Bottom Feed 2500A 210 THPC3625BG3T Bottom Feed 3000A 210 THPC3630BG3T Bottom Feed 4000A 540 THPC3640BG3T HPC ™ Switches with Integral Ground Fault Alarm only for Solidly Grounded Systems Integral Ground Fault with 3-Phase Sensor, Adjustable Pick-up, Adjustable Time-Delay, Test Function, and Mechanical Ground Fault Indicator Source Ampere Net Weight Product Configuration Rating Lbs. (Approx.) Number Top Feed 800A 105 THPR3608GA3 Top Feed 1200A 105 THPR3612GA3 Top Feed 1600A 105 THPR3616GA3 Top Feed 2000A 195 THPC3620GA3 Top Feed 2500A 210 THPC3625GA3 Top Feed 3000A 210 THPC3630GA3 Top Feed 4000A 540 THPC3640GA3 Bottom Feed 800A 105 THPR3608BGA3 Bottom Feed 1200A 105 THPR3612BGA3 Bottom Feed 1600A 105 THPR3616BGA3 Bottom Feed 2000A 195 THPC3620BGA3 Bottom Feed 2500A 210 THPC3625BGA3 Bottom Feed 3000A 210 THPC3630BGA3 Bottom Feed 4000A 540 THPC3640BGA3 Includes fuse-mounting hardware and door-catch interlock bracket. (Fuses not included) NOTE: The 800-3000 ampere integral ground fault HPC ™ switches can easily be installed in the space occupied by a manual HPC ™ switch of the same ampere rating. The 4000 ampere switch, being 3 inches wider, may require some modification. NOTE: Integral ground fault tripping is accomplished by a low-energy, flux-shifting tripping mechanism and is not suitable for remote (paralleled) tripping. If remote tripping is required, add suffix RT1 120-240Vac or RT2 480-600Vac to above product number.

HPC ™ Switches with Integral Ground Fault Protection

Integral Ground Fault HPC ™ Pick-up and Delay Time-current Curves NOTE: OBSOLETE, SEE PAGE 9-6 FOR NEW HPC ™ PRODUCT NUMBERS. 1. Mechanical Indicator – protrudes when ground fault occurs. 2. Field Adjustable Ground Fault Trip Point – from 200 to 1100 amperes in six steps. 3. Field Adjustable Ground Fault Delay Time – min. (0.03 sec.) intermediate (0.20 sec.) and max. (0.50 sec.) delay time settings. 4. No Trip Test Button – permits ground fault system check without tripping switch. 5. Test Button – simulates an actual ground fault and will trip switch off unless "No Trip" button is depressed prior to pushing test button. Ground fault indicator will protrude when system is tested or when actual ground fault occurs. Note: Although the integral ground fault function is self-powered, the test function does require an external 120Vac (200 volt amperes nominal) control power source.

Rev. 1/19 Data subject to change without notice

GE Products BuyLog

go.abb/industrial

9-4

Made with FlippingBook - Online magazine maker