GE Products BuyLog Smart Catalog

Modular Metering

Section 2

Mini Mod III Ring-Type and Ringless

Product Features —— UL Listed (Panelboards No. 67) —— Indoor/Outdoor construction —— Ring-Type and Ringless Meter Sockets —— Bondable Neutral, Strap included —— 11-inch Mounting Z Rail included —— Swing Away Mounting Feet factory installed —— Underground, incoming feed only

Main Ampere Rating

Ringless Type Socket (5th Jaw Socket Standard) Horned Bypass Factory Installed

Main Wire Size AWG/kcmil Cu/Al - Phase

Socket Amps

No. of Sockets

Ring-Type Socket 1 TMM2212R 2

Ringless Type Socket

Service Ground

Equipment Ground

2

200

TMMR2212R 2

TMMR2212RHB 2

(1) 6-300

6-2/0

3 4

400 400

TMM4312R

TMMR4312R

TMMR4312RHB

(1) 6-600 or (2) 2/0-250

125

TMM4412R

TMMR4412R

TMMR4412RHB

14-4

4-300

5

600

TMM6512R

TMMR6512R

TMMR6512RHB

(2) 250-500

6 2 3 4 5 6

600

TMM6612R

TMMR6612R

TMMR6612RHB

400 600 600 600 600

TMM4220R

TMMR4220R

TMMR4220RHB

6-2/0

TMM6320R

TMMR6320R

TMMR6320RHB

200

TMM6420R

TMMR6420R

TMMR6420RHB

(2) 250-500

14-4

4-300

TMM6520R

TMMR6520R

TMMR6520RHB

TMM6620R

TMMR6620R

TMMR6620RHB

1 One snap-type, aluminum sealing ring (TSR5) per socket included 2 May be fed from overhead. Use hub TC300.

Short Circuit Ratings — UL Listed All Mini Mod IIIs are UL listed for the short circuit rating at 240 Vac maximum in rms symmetrical amperes of the tenant breaker installed, selected from table below. The short circuit rating is limited to the lowest interrupting rating of any tenant breaker installed. Replacement breakers shall be of the same manufacturer and type and shall have an interrupting rating equal to or greater than the interrupting rating of any tenant breaker presently installed in this device.

Breaker Amperage Range

Socket Amperage Range

UL Listed AIC Rating

Tenant Main Breaker Frame

TEB

15-90A

225A

10,000

THQL

60-125A

125A

10,000

TQD

100-225A

200A, 225A

10,000

THHQL

60-125A

125A

22,000

THQD

100-225A

200A, 225A

22,000

TMQL

60-125A

125A

42,000

TMQC

60-200A

200A/225A

42,000

TMQA

60-125A

125A

65,000

TMQF

60-200A

200A/225A

65,000

TMQV (Replaces Old TMQD)

60-225A

200A, 225A

100,000

Rev. 1/19 Data subject to change without notice