Switchboards Spectra ™ Series Switchboards Spectra ™ Series Plug-in Switchboards Pro-Stock Nomenclature
Section 12
SWPS
200
M C T N1 EPM
Amperage 120= 1200A
Metering
Blank= Without Metering EPM= With Metering 3 3 EPM 2200 included in this section
160= 1600A 200= 2000A
Feed Type M= Main Breaker L= Main Lugs
Enclosure
N1= NEMA 1 N3= NEMA 3R
D= Splice To Existing 1 1 Only For Distribution Sections
Feed Location T= Top Feed
Bus C= Copper A= Aluminum
B= Bottom Feed Blank= Center 2
2 Only For Distribution Sections splicing to an existing section
Technical Data
Product Capability/Specification
Pro-Stock Switchboard
Enclosure Types
NEMA 1
45" W x 90" H x 30" D (1200A NEMA 1) 45" W x 90" H x 35" D (1600-2000A NEMA 1)
Section Dimensions
208/120Vac 3 Phase 4 Wire 60Hz 480/277Vac 3 Phase 4 Wire 60Hz
Voltage
1200A 1600A 2000A
Amperage
Panel Type
Spectra Plug-In (C/B Feeders Only)
Main Breaker and Distribution Section: 38X (1200A) & 18X (1600-2000A) Distribution Section: 38X (1200-2000A)
Panel Size
Copper (1000 A/Sq. In.) Aluminum (750 A/Sq. In) UL, NEMA, NEC, PB II
Bus Bar
Standards
Seismic Rating
Qualified for Seismic Ratings per publication DET-463 and OSP-0044-10
Entry
Cable
Feed Location
Top or Bottom Feed Mechanical Aluminum Copper or Aluminum
Lug Type
Incoming Cable Feed Direction
Right, Left or Both Front Access Only
Access
Bus Bracing
65000A
Rated to 65kAIC at 480/277Vac max. The short circuit rating of any switchboard section is limited to the lowest short circuit rating of any installed device.
Device S/C Rating
Neutral Rating
100% Rating
1200A to 2000A ETU (LSIG) Programmer
Main Devices
Delivery Time
2 Weeks to Ship, 3 Weeks On-Site
Rev. 1/19 Data subject to change without notice