GE Products BuyLog Smart Catalog
Uninterruptible Power Supplies Energy Connections VH Series VH 2000 - 3000 UL/208V
Section 20
Optional features SNMP interface card
Battery modules – extended runtime Additional battery modules (up to 3) may be connected in parallel to in order to achieve a longer runtime. Every battery module is equipped with its DC cabling and it makes connection between modules very easy and simple. Increasing of total battery capacity will correspond to a longer recharging time.
An SNMP interface adapter can be placed in the SNMP slot in the rear panel of the UPS, which allows the data interface to be con- nected directly to an Ethernet or Web. USB/RS232/Relay Card The card is provided with an USB connector, a 9-pole sub-D con- nector and four potential free changeover contacts, representing: mains failure, general alarm, battery low and bypass active.
Table.1 Dimensions and battery run times
No. of extra battery cabinets
Battery cabinet
UPS cabinet
Backup time (min.)
Total capacity (Ah)
UPS Model
Dimensions (HxWxD)
Shipping weight
Dimensions (HxWxD)
Shipping weight
Weight
Weight
5
7
– 1 2 3 – 1 2 3
30 60 90 15 25 50 4
21 35 49 23 37 51 9
VH2000
66 lbs / 30 kg
68 lbs / 31 kg
9.0x7.4x23.6 inch 228x188x600 mm
88 lbs 40 kg
110 lbs 50 kg
9.0x7.4x23.4 inch 228x188x595 mm
VH3000
68 lbs / 31 kg
73 lbs / 33 kg
Protections and cable sections
Cable sections input and output recommended by NEC standards Alternatively, local standards to be respected
Recommended external fusing of input wiring
CABLE SECTIONS (90° C insulation) mm 2 AWG
UPS Model
Mains / Bypass input
VH2000 VH3000
3.33 5.26
12 10
20A Class "B" MCB
Rev. 1/19 Data subject to change without notice
GE Products BuyLog
go.abb/industrial
20-12
Made with FlippingBook - Online magazine maker